With respect to the free vertical space between the car roof and the well ceiling, Liftinstsitutt stated, in a letter to Orona of 10 July 2015, supporting Orona’s considerations, that ‘a guaranteed minimum free space of 0,5 m is generally accepted as sufficient to avoid the danger of crushing the human body […]. That this is also acceptable for application in lifts is reflected in EN 81-1:1998+A3:2009, clause 5.7.3.3 b)’. In any case, Orona stated in its observations of 18 May 2016 that the block above the car of the M33v3 lift has the same vertical clearance (0,5 m) as the vertical clearance required under EN 81-1 for the rescue space below the car (in the well). As for the free space volume (cube), as described in the technical specifications of the M33v3 lift, the block above the car of the lift has a greater volume (0,5 m × 0,7 m × 1,0 m) than the minimum volume required under EN 81-1 for both the rescue space above the car (0,5 m × 0,6 m × 0,8 m) and the rescue space below the car (0,5 m × 0,6 m × 1,0 m). A study requested by Orona and sent to the Commission on 15 March 2016, carried out by a technology centre specialised in product, process and service innovation named IK4-Ikerlan (‘the IK4-Ikerlan study’), shows that all the maintenance personnel tested (representative of the usual variety of maintenance personnel, aged between 18 and 65, and male) fit within the cube above the car of the lift, while this was not the case in the cube dimensioned in accordance with EN 81-1.
27 2. POSITIONS AND ARGUMENTS OF THE PARTIES › 2.2. Position and arguments of Orona, Decision_act (EU) 2021/534
In forcesince 24 Mar 2021