Voltage range | Time period for operation
0,85 pu-0,90 pu | 60 minutes
0,90 pu-1,10 pu | Unlimited
1,10 pu-1,12 pu | Unlimited, unless specified otherwise by the relevant system operator, in coordination with the relevant TSO.
1,12 pu-1,15 pu | To be specified by the relevant system operator, in coordination with the relevant TSO.
Table 12: Minimum time periods for which a remote-end HVDC converter station shall be capable of operating for different voltages deviating from a reference 1 pu value without disconnecting from the network where the voltage base for pu values is from 110 kV to (not including) 300 kV.
Voltage range | Time period for operation
0,85 pu-0,90 pu | 60 minutes
0,90 pu-1,05 pu | Unlimited
1,05 pu-1,15 pu | To be specified by the relevant system operator, in coordination with the relevant TSO. Various sub-ranges of voltage withstand capability may be specified.
Table 13: Minimum time periods for which a remote-end HVDC converter station shall be capable of operating for different voltages deviating from a reference 1 pu value without disconnecting from the network where the voltage base for pu values is from 300 kV to 400 kV (included).
Maximum range of Q/Pmax | Maximum range of steady-state voltage level in PU
0,95 | 0,225
Table 14: Maximum range of both Q/Pmax and steady-state voltage for a remote-end HVDC converter station.