Frequency range | Time period for operation
47,0 Hz-47,5 Hz | 20 seconds
47,5 Hz-49,0 Hz | 90 minutes
49,0 Hz-51,0 Hz | Unlimited
51,0 Hz-51,5 Hz | 90 minutes
51,5 Hz-52,0 Hz | 15 minutes
Table 8: Minimum time periods for the 50 Hz nominal system for which a PPM shall be capable of operating for different frequencies deviating from a nominal value without disconnecting from the network.