ANNEX V, Regulation (EU) 2016/1447

In forcesince 26 Aug 2016

Figure 6: Fault-ride-through profile of an HVDC converter station. The diagram represents the lower limit of a voltage-against-time profile at the connection point, expressed by the ratio of its actual value and its reference 1 pu value in per unit before, during and after a fault. Uret is the retained voltage at the connection point during a fault, tclear is the instant when the fault has been cleared, Urec1 and trec1 specify a point of lower limits of voltage recovery following fault clearance. Ublock is the blocking voltage at the connection point. The time values referred to are measured from tfault.

Voltage parameters [pu] | Time parameters [seconds]

Uret | 0,00-0,30 | tclear | 0,14-0,25

Urec1 | 0,25-0,85 | trec1 | 1,5-2,5

Urec2 | 0,85-0,90 | trec2 | Trec1-10,0

Table 7: Parameters for Figure 6 for the fault-ride-through capability of an HVDC converter station.