ANNEX III, Regulation (EU) 2016/1447

In forcesince 26 Aug 2016

Synchronous Area | Voltage Range | Time period for operation

Continental Europe | 0,85 pu-1,118 pu | Unlimited

1,118 pu-1,15 pu | To be established by each relevant system operator, in coordination with the relevant TSO but not less than 20 minutes

Nordic | 0,90 pu-1,05 pu | Unlimited

1,05 pu-1,10 pu | 60 minutes

Great Britain | 0,90 pu-1,10 pu | Unlimited

Ireland and Northern Ireland | 0,90 pu-1,118 pu | Unlimited

Baltic | 0,85 pu-1,118 pu | Unlimited

1,118 pu-1,15 pu | 20 minutes

Table 4: Minimum time periods an HVDC system shall be capable of operating for voltages deviating from the reference 1 pu value at the connection points without disconnecting from the network. This table applies in case of pu voltage base values at or above 110 kV and up to (not including) 300 kV.

Synchronous Area | Voltage Range | Time period for operation

Continental Europe | 0,85 pu-1,05 pu | Unlimited

1,05 pu-1,0875 pu | To be specified by each TSO, but not less than 60 minutes

1,0875 pu-1,10 pu | 60 minutes

Nordic | 0,90 pu-1,05 pu | Unlimited

1,05 pu-1,10 pu | To be specified by each TSO, but not more than 60 minutes

Great Britain | 0,90 pu-1,05 pu | Unlimited

1,05 pu-1,10 pu | 15 minutes

Ireland and Northern Ireland | 0,90 pu-1,05 pu | Unlimited

Baltic | 0,88 pu-1,097 pu | Unlimited

1,097 pu-1,15 pu | 20 minutes

Table 5: Minimum time periods an HVDC system shall be capable of operating for voltages deviating from the reference 1 pu value at the connection points without disconnecting from the network. This table applies in case of pu voltage base values from 300 kV to 400 kV (included).