TABLE 1
PARAMETERS AND CIRCUMSTANCES FOR CHECK MONITORING
…
TABLE 2
ANNUAL SAMPLING FREQUENCIES: WATER SUPPLY ZONES
…
TABLE 3
ANNUAL SAMPLING FREQUENCIES: SUPPLY POINTS
…
TABLE 4
ANNUAL SAMPLING FREQUENCIES: WATER TREATMENT WORKS
…
TABLE 1
PARAMETERS AND CIRCUMSTANCES FOR CHECK MONITORING
…
TABLE 2
ANNUAL SAMPLING FREQUENCIES: WATER SUPPLY ZONES
…
TABLE 3
ANNUAL SAMPLING FREQUENCIES: SUPPLY POINTS
…
TABLE 4
ANNUAL SAMPLING FREQUENCIES: WATER TREATMENT WORKS
…
The Water Quality (Scotland) Regulations 2010Law
… disinfection and to verify the performance of the disinfection process. Regulation 14 substitutes Tables 2, 3 and 4 in Schedule 3 to the 2001 Regulations. Regulations 15- 20 amend the 2006 Regulations in consequence of the new sections …
(1) | (2) | (3)
Item | Parameter | Circumstances
1. | Aluminium | – When used as flocculant or where the water originates from, or is influenced by, surface waters
2. | Ammonium |
3. | Clostridium perfringens (including spores) | – Where the water originates from, or is influenced by, surface waters
4. | Coliform bacteria |
5. | Colony counts |
6. | Colour |
7. | Conductivity |
8. | Escherichia coli (E. Coli) |
9. | Hydrogen ion |
10. | Iron | – When used as flocculant or where the water originates from, or is influenced by, surface waters
11. | Manganese | – Where the water originates from, or is influenced by, surface waters
12. | Nitrate | – When chloramination is practised
13. | Nitrite | – When chloramination is practised
14. | Odour |
15. | Taste |
16. | Turbidity |…
(1) | (2) | (3) | (4)
Substances and parameters subject to check monitoring | Estimated population of water supply zone | Reduced | Standard
Notes:
+
See regulation 6(2) and Table 1 in Schedule 3.
*
Sampling for these parameters may be within water supply zones or at supply points as specified in Table 3, subject to notes (ii) and (iii) below.
(i)
Where the population is not an exact multiple of 5000, the population figure should be rounded up to the nearest multiple of 5000.
(ii)
Audit monitoring in water supply zones is required only where sodium hypochlorite is added after water has left the treatment works. In other circumstances, audit monitoring is required at supply points.
(iii)
To monitor for total indicative dose (for radioactivity).
E.Coli | <100 | | 4
Coliform bacteria Residual disinfectant | ≥100 | | 12 per 5000 population
Aluminium | | |
Ammonium | | |
Clostridium perfringes (including spores) | | |
Colony counts | <100 | 1 | 2
Colour | 100 – 4,999 | 2 | 4
Conductivity | 5,000 – 9,999 | 6 | 12
Hydrogen ion | 10,000 – 29,999 | 12 | 24
Iron | 30,000 – 49,999 | 18 | 36
Manganese | 50,000 – 79,999 | 26 | 52
Nitrate | 80,000 – 100,000 | 38 | 76
Nitrite | | |
Odour | | |
Taste | | |
Turbidity | | |
Parameters subject to audit monitoring | | |
Antimony | | |
Arsenic | | |
Benzene | | |
Benzo(a)pyrene | | |
Boron | | |
Bromate | | |
Cadmium | | |
Chromium | <100 | | 1
Copper | 100 – 4,999 | | 4
Cyanide | 5,000 – 100,000 | | 8
1, 2 dichloroethane | | |
Enterococci | | |
Flouride | | |
Lead | | |
Mercury | | |
Nickel | | |
Pesticides | | |
PAH | | |
Selenium | | |
Sodium | | |
Trichloroethene/Tetrachloroethene | | |
Tetrachloromethane | <100 | | 1
THM | 100 – 4,999 | | 4
Chloride | 5,000 – 100,000 | | 8
Sulphate | | |
Total Organic Carbon | | |
Tritium | | |
Gross alpha | | |
Gross beta | | |…
(1) | (2) | (3) | (4) | (5)
Item | Substances and parameters subject to check monitoring | Volume of water supplied m3/d | Reduced | Standard
Notes:
(i)
Check monitoring is required only in respect of surface waters (see regulation 6(2) and Table 1 in Schedule 3), otherwise audit monitoring.
(ii)
Audit monitoring at supply points is permitted only where sodium hypochlorite is not added after water has left the treatment works. In other circumstances, audit monitoring is required in water supply zones.
(iii)
To monitor for total indicative dose (for radioactivity).
1. | Clostridium perfringens (including spores) | <20 | | 2
20 – 999 | 2 | 4
2. | Conductivity | 1,000 – 1,999 | 6 | 12
2,000 – 5,999 | 12 | 24
6,000 – 9,999 | 18 | 36
10,000 – 15,999 | 26 | 52
16,000 – 32,999 | 52 | 104
33,000 – 49,999 | 78 | 156
50,000 – 67,999 | 104 | 208
68,000 – 84,999 | 130 | 260
85,000 – 101,999 | 156 | 312
102,000 – 119,999 | 183 | 365
120,000 – 241,999 | 365 | 730
242,000 – 484,999 | 730 | 1,460
485,000 – 728,999 | 1,095 | 2,190
Parameters subject to audit monitoring | | |
3. | Benzene | | |
4. | Boron | | |
5. | Bromate | | |
6. | Cyanide | | |
7. | 1,2 dichloroethane | | |
8. | Fluoride | <20 | | 1
9. | Mercury | 20 – 999 | | 4
10. | Pesticides | 1,000 – 49,999 | | 8
11. | Trichloroethene/Tetrachloroethene | 50,000 – 89,999 | | 12
90,000 – 299,999 | | 24
12. | Tetrachloromethane | 300,000 – 649,999 | | 36
13. | Chloride | ≥650,000 | | 48
14. | Sulphate | | |
15. | Total organic carbon | | |
16. | Tritium | | |
17. | Gross alpha | | |
18. | Gross beta | | |…
(1) | (2) | (3) | (4) | (5)
Item | Substances and parameters subject to check monitoring | Volume of water supplied m3/d | Reduced | Standard
Notes:
(i)
check monitoring at treatment works is required only when chloramination is practised. In other circumstances, audit monitoring is required.
1. | E. coli | <20 | | 4
2. | Coliform bacteria | 20 – 1,999 | 12 | 52
3. | Colony counts | 2,000 – 5,999 | 52 | 104
4. | Residual disinfectant | 6,000 – 11,999 | 104 | 208
≥12,000 | 104 | 365
5. | Nitrite | <20 | | 2
6. | Turbidity | 20 – 999 | 2 | 4
1,000 – 1,999 | 6 | 12
2,000 – 5,999 | 12 | 24
6,000 – 9,999 | 18 | 36
10,000 – 15,999 | 26 | 52
16,000 – 32,999 | 52 | 104
33,000 – 49,999 | 78 | 156
50,000 – 67,999 | 104 | 208
68,000 – 84,999 | 130 | 260
85,000 – 101,999 | 156 | 312
102,000 – 119,999 | 183 | 365
120,000 – 241,999 | 365 | 730
242,000 – 484,999 | 730 | 1,460
485,000 – 728,999 | 1,095 | 2,190
Substances and parameters subject to audit monitoring | | |
7. | Nitrite | <20 | | 1
20 – 999 | | 4
1,000 – 49,999 | | 8
50,000 – 89,999 | | 12
90,000 – 299,999 | | 24
300,000 – 649,999 | | 36
>650,000 | | 48…