Schedule 2 INDICATOR PARAMETERS, The Water Supply (Water Quality) (Scotland) Regulations 2001 (revoked)
Changed on 1 Jan 2015
Item | Parameters | Concentration or Value (maximum) or State | Units of Measurement | Point of monitoring
Notes:
(i)
The water should not be aggressive.
(ii)
Excluding tritium, potassium – 40, radon and radon decay products.
*
May be monitored from samples of water leaving treatment works or other supply point, as no significant change during distribution.
1. | Ammonium | 0.50 | mgNH4/l | consumers' taps
2. | Chloride | 250 | mgCl/l | supply point
3. | Clostridium perfringens (including spores) | 0 | Number/100 ml | supply point
4. | Coliform bacteria | 0 | Number/100ml | consumers' taps
5. | Colony count | No abnormal change | Number/1 ml at 22°C | consumers' taps
Number/1 ml at 37°C | service reservoirs and treatment works
6. | Conductivity | 2500 | μS/cm at 20°C | supply point
7. | Sulphate | 250 | mgSO4/l | supply point
8. | Total indicative dose (for radioactivity) | 0.10 | mSv/year | supply point
9. | Total organic carbon (TOC) | No abnormal change | mgC/l | supply point
10. | Tritium (for radioactivity) | 100 | Bq/l | supply point
11. | Turbidity | 1 | NTU | treatment works…
- 1 Jan 2015 – todayin force
- 4 Jun 2001 – 1 Jan 2015earlier wording