The maximum values relate to the achievable efficiency grade N (minimum efficiency formulas are set out in Annex II) with clean air and no space and/or noise restrictions. The minimum values apply to contaminated air (some dust load) and space, noise and/or other operational restrictions at the limit of what is still in scope according to the exemptions in Article 1.
Fan type | Measurement category | Pressure |
N
minimum
N
maximum
Axial fans | A, C | static | 50 | 75
B, D | total | 64 | 85
Forward curved < 5 kW and backward inclined fans | A, C | static | 52 | 65
B, D | total | 57 | 70
Forward curved ≥ 5 kW, backward curved fans | A, C | static | 64 | 80
B, D | total | 67 | 85
Mixed flow fans | A, C | static | 57 + 7 • (α –45) / 25 | 77
B, D | total | 67 | 85
Jet fans | E | | 50 | 60
Cross flow fans: 21 % efficiency.