ANNEX I, Regulation (EU) 2024/1834

In forcesince 28 Dec 2025cited 1×
(1)

‘measurement category’ means a test, measurement or usage arrangement that defines the inlet and outlet conditions of the fan being tested;

(2)

‘measurement category A’ means an arrangement where the fan is measured with free inlet and outlet conditions, and a partition between inlet and outlet zone;

(3)

‘measurement category B’ means an arrangement where the fan is measured with free inlet and with a duct fitted to its outlet, and a partition between inlet and outlet zone;

(4)

‘measurement category C’ means an arrangement where the fan is measured with a duct fitted to its inlet and free outlet conditions, and a partition between inlet and outlet zone;

(5)

‘measurement category D’ means an arrangement where the fan is measured with a duct fitted to its inlet and outlet, and a partition between inlet and outlet zone;

(6)

‘measurement category E’ means an arrangement where the fan is measured with free inlet and outlet conditions, and without a partition between inlet and outlet zone;

(7)

‘efficiency category’ means the fan gas output energy form used to determine the fan energy efficiency, with a distinction for all fans except jet fans between ‘static’ or ‘total’ efficiency depending on whether the fan gas power has been determined with respectively the fan static pressure or fan pressure;

(8)

‘fan efficiency’ (η) means the ratio of the fan gas power output Pu and the electric input power Pe, both expressed in W and determined at BEP, multiplied with correction factors for power conversion Cp, part load compensation Cc and guard compensation Cguard, with a distinction between ‘static’ or ‘total’ efficiency depending on whether the fan gas power Pu has been determined with respectively the fan static pressure or fan pressure, in accordance with point 6.1 of Annex III;

(9)

‘fan gas power’ (Pu), in W, means the product of the volume flow rate qv, in m3/s, and the applicable pressure difference between fan inlet and outlet Δp (fan pressure or fan static pressure), in Pa, both determined at BEP, with a distinction between ‘static’ or ‘total’ fan gas power depending on whether the fan gas power has been determined with, respectively, the fan static pressure or fan pressure;

(10)

‘electric input power’ (Pe), in W, means the electric input power at BEP or Tm, measured at main terminals of motor or, when present, of variable speed drive;

(11)

‘power conversion correction’ (Cp), means a correction factor for power conversion losses, as determined according to point 6 of Annex III;

(12)

‘part load compensation’ (Cc) means a correction factor for part load, as determined according to point 6 of Annex III;

(13)

‘guard compensation’ (Cguard) means a correction factor, as determined according to point 6 of Annex III, that may be applied when calculating fan efficiency where the fan is equipped with permanently fitted protective guards that cannot be removed without making the fan inoperable;

(14)

‘volume flow rate’ (qv), in m3/s, means the gas volume displaced per unit of time by the fan and is derived from the mass flow rate, typically with standard air with a density ρ at default 1,2 kg/m3;

(15)

‘total pressure’ (ptot), in Pa, means the pressure calculated from the absolute pressure and the dynamic pressure;

(16)

‘absolute pressure’ (p), in Pa, means the pressure measured with respect to absolute zero pressure;

(17)

‘dynamic pressure’ (pd), in Pa, means the pressure calculated from the velocity and the density;

(18)

‘fan static pressure’ (pfs), in Pa, means the difference between the static pressure at the fan outlet and the stagnation pressure at the fan inlet or, when the compressibility phenomenon is not a factor, the difference between the static pressure at the fan outlet and the total pressure at the fan inlet. It is the omnidirectional force per unit surface area exerted at the fan outlet and is typically assessed by measuring the stagnation pressure in a (cylindrical) hole of appropriate geometry and dimensions, in duct wall or appropriate measurement instrument perpendicular to the direction of the gas flow;

(19)

‘fan pressure’ (pf), in Pa, means the difference between the stagnation pressures at the fan outlet and the fan inlet or, when compressibility phenomenon is not a factor, the difference between the total pressures at the fan outlet and the fan inlet. It is the directional force per unit surface area exerted at the fan outlet and is typically assessed by measuring the stagnation pressure in a (cylindrical) hole of appropriate geometry and dimensions facing the direction of the gas flow;

(20)

‘stagnation pressure’ (psg), in Pa, means the pressure measured at a point in a flowing gas if it were brought to rest via a process where there is no transfer of heat or matter;

(21)

‘efficiency grade’ means a parameter in the calculation of the minimum energy efficiency of a fan of specific electric input power at its BEP or at Tm (expressed as parameter ‘N’ in the calculation of the fan energy efficiency);

(22)

‘minimum fan efficiency’ (ηmin) means the fan efficiency to be achieved in order to meet the requirements, calculated as the outcome of the appropriate equation in Annex II, using the applicable integer N of the efficiency grade and the electric input power Pe of the fan expressed in kW at its BEP;

(23)

‘minimum jet fan efficiency (ηr,min)’ means fan efficiency to be achieved in order to meet the requirements, calculated as the outcome of the appropriate equation in Annex II, using the applicable integer N of the efficiency grade and the electric input power Pe of the fan expressed in kW at its measured thrust;

(24)

‘measured thrust (Tm)’ is the jet fan thrust measured, in N, assessed according to measurement category E and converted to the density of 1,2;

(25)

‘jet-fan efficiency’ηr(T) means the fan gas power output derived from the measured thrust of a jet fan divided by the electric input power Pe, multiplied with correction factors for power conversion Cp, part load compensation Cc and guard compensation Cguard, in accordance with point 6.2 of Annex III;

(26)

‘specific speed’ (σΒΕΡ) means the ratio between volume flow rate and fan pressure as dimensionless characteristic number determined at BEP, in accordance with point 8 of Annex III;

(27)

‘low noise fan’ means an axial fan with an electric input power of 10 kW or more with a maximum characteristic noise emission value L ≤ 32 dB(A) at BEP;

(28)

‘dual use fan’ means a fan designed for both ventilation under normal conditions and emergency use as set out in Article 1(3), point (b);

(29)

‘reversible fan’ means a fan capable of reaching at least 80 % of the nominal forward volume flow rate in the reverse direction;

(30)

‘custom fan’ means a fan having a custom design for a specific customer and/or contract with respect to one or more of the significant elements, and an operating point or range specified by the customer/contract. These fans are only supplied to that customer/contract. Details are not presented in catalogues, online media or general selection tools. The performance details are specific to the application and the customer/contract;

(31)

‘safety critical fan’ means a fan that has been designed, verified, certified and manufactured under the scope of either the Regulation (EU) No 305/2011 or Directive 2014/34/EU relating to equipment and protective systems intended for use in potentially explosive atmospheres;

(32)

‘professional repairer’ means an operator or undertaking which provides services of repair and professional maintenance of fans;

(33)

‘manufacturer-authorised professional repairer’ means a professional repairer authorised by the manufacturer, importer or authorised representative to repair safety critical fans they place on the market;

(34)

‘wearing parts (sacrificial elements)’ means parts that are intentionally designed to wear, for the fan to meet the requirements of its intended use. For example, where a fan is used in an abrasive environment the fan can quickly become damaged by the abrasion. Some parts are designed as sacrificial elements to protect other critical areas and are designed to be replaced more frequently;

(35)

‘proprietary tool’ means a tool that is not commonly available and is specifically designed for a function that cannot be safely and/or reliably achieved by a commonly available tool;

(36)

‘inherent speed’ means the rotation speed of the fan, when the fan is operated at nominal or rated supply conditions of the motor;

(37)

‘guarantee’ means any undertaking by the manufacturer, importer or authorised representative to the consumer, to: (a) reimburse the price paid; or (b) replace, repair or handle fans in any way if they do not meet the specifications set out in the guarantee statement or in the relevant advertising;

(38)

‘spare part’ means a separate part that can replace a part with the same or similar function in a fan;

(39)

‘spare part fan’ means a fan intended to replace a corresponding existing fan that is integrated into a product;

(40)

‘tip speed’(utip), in m/s, means the peripheral speed of the impeller blade tips;

(41)

‘impeller diameter’ (Dimpeller), in mm, means the maximum diameter measured over the tips of the blades of the impeller.