FCR technical minimum requirements referred to in Article 154:
Minimum accuracy of frequency measurement | CE, GB, IE/NI and Nordic | 10 mHz or the industrial standard if better
Maximum combined effect of inherent frequency response insensitivity and possible intentional frequency response dead band of the governor of the FCR providing units or FCR providing groups. | CE | 10 mHz
GB | 15 mHz
IE/NI | 15 mHz
Nordic | 10 mHz
FCR full activation time | CE | 30 s
GB | 10 s
IE/NI | 15 s
Nordic | 30 s if system frequency is outside standard frequency range
FCR full activation frequency deviation. | CE | ± 200 mHz
GB | ± 500 mHz
IE/NI | Dynamic FCR ± 500 mHz
Static FCR ± 1000 mHz
Nordic | ± 500 mHz