Frequency quality defining parameters referred to in Article 127:
CE | GB | IE/NI | Nordic
standard frequency range | ± 50 mHz | ± 200 mHz | ± 200 mHz | ± 100 mHz
maximum instantaneous frequency deviation | 800 mHz | 800 mHz | 1000 mHz | 1000 mHz
maximum steady-state frequency deviation | 200 mHz | 500 mHz | 500 mHz | 500 mHz
time to recover frequency | not used | 1 minute | 1 minute | not used
frequency recovery range | not used | ± 500 mHz | ± 500 mHz | not used
time to restore frequency | 15 minutes | 15 minutes | 15 minutes | 15 minutes
frequency restoration range | not used | ± 200 mHz | ± 200 mHz | ± 100 mHz
alert state trigger time | 5 minutes | 10 minutes | 10 minutes | 5 minutes
Frequency quality target parameters referred to in Article 127:
CE | GB | IE/NI | Nordic
maximum number of minutes outside the standard frequency range | 15000 | 15000 | 15000 | 15000