1.
For the purposes of compliance and verification of compliance with the requirements of this Regulation, measurements and calculations shall be made using harmonised standards the reference numbers of which have been published for this purpose in the Official Journal of the European Union, or using other reliable, accurate and reproducible methods that take into account the generally recognised state-of-the-art methods. They shall meet the conditions and technical parameters set out in points 2 to 5.
Solid fuel boilers shall be tested with the preferred fuel.
The declared value for the seasonal space heating energy efficiency shall be rounded to the nearest integer.
The useful efficiency values ηn, ηp and the useful heat output values Pn, Pp shall be measured, as appropriate. For solid fuel cogeneration boilers the electrical efficiency value ηel,n is also measured.
The seasonal space heating energy efficiency ηs shall be calculated as the seasonal space heating energy efficiency in active mode ηson, corrected by contributions accounting for temperature controls, auxiliary electricity consumption, and, for solid fuel cogeneration boilers, by adding the electrical efficiency multiplied by a conversion coefficient CC of 2,5;
The consumption of electricity shall be multiplied by a conversion coefficient CC of 2,5.
Seasonal space heating energy efficiency ηs is defined as:
ηs = ηson – F(1) – F(2) + F(3)
where:
ηson is the seasonal space heating energy efficiency in active mode, expressed as a percentage, calculated as set out in point 4(b);
F(1) accounts for a loss of seasonal space heating energy efficiency due to adjusted contributions of temperature controls; F(1) = 3 %;
F(2) accounts for a negative contribution to the seasonal space heating energy efficiency by auxiliary electricity consumption, expressed as a percentage, and is calculated as set out in point 4(c);
F(3) accounts for a positive contribution to the seasonal space heating energy efficiency by the electrical efficiency of solid fuel cogeneration boilers, expressed as a percentage, and is calculated as follows:
F(3) = 2,5 × ηel,n
the seasonal space heating energy efficiency in active mode, ηson, is calculated as follows:
for manually stoked solid fuel boilers that can be operated at 50 % of the rated heat output in continuous mode, and for automatically stoked solid fuel boilers:
ηson = 0,85 × ηp + 0,15 × ηn
for manually stoked solid fuel boilers that cannot be operated at 50 % or less of the rated heat output in continuous mode, and for solid fuel cogeneration boilers:
ηson = ηn
F(2) is calculated as follows:
for manually stoked solid fuel boilers that can be operated at 50 % of the rated heat output in continuous mode, and for automatically stoked solid fuel boilers:
F(2) = 2,5 × (0,15 × elmax + 0,85 × elmin + 1,3 × PSB)/(0,15 × Pn + 0,85 × Pp)
for manually stoked solid fuel boilers that cannot be operated at 50 % or less of the rated heat output in continuous mode, and for solid fuel cogeneration boilers:
F(2) = 2,5 × (elmax + 1,3 × PSB)/Pn
The gross calorific value (GCV) shall be obtained from the gross calorific value moisture free (GCVmf) by applying the following conversion:
GCV = GCVmf × (1 – M)
where:
GCV and GCVmf are expressed in megajoules per kilogram;
M is the moisture content of the fuel, expressed as a proportion.