ANNEX VIII Calculation of the specific energy consumption requirement, Commission Regulation (EU) No 1253/2014 of 7 July 2014 implementing Directive 2009/125/E…

In forcesince 7 Jul 2014

The specific energy consumption SEC is calculated with the following equation:

SECtapefqnetMISCCTRLxSPIthΔΤhηh– 1cairqrefqnetCTRLMISC1ηtQdefr

where:

SEC is Specific Energy Consumption for ventilation per m2 heated floor area of a dwelling or building [kWh/(m2.a)];

ta is annual operating hours [h/a];

pef is primary energy factor for electric power generation and distribution [-];

qnet is net ventilation rate demand per m2 heated floor area [m3/h.m2];

MISC is an aggregated general typology factor, incorporating factors for ventilation effectiveness, duct leakage and extra infiltration [-];

CTRL is ventilation control factor [-];

x is an exponent that takes into account non-linearity between thermal energy and electricity saving, depending on motor and drive characteristics [-];

SPI is Specific Power Input [kW/(m3/h)];

th is total hours heating season [h];

ΔΤh is the average difference in indoor (19 °C) and outdoor temperature over a heating season, minus 3K correction for solar and internal gains [K];

ηh is the average space heating efficiency [-];

cair is the specific heat capacity of air at constant pressure and density [kWh/(m3 K)];

qref is the reference natural ventilation rate per m2 heated floor area [m3/h.m2];

ηt is the thermal efficiency of heat recovery [-];

Qdefr is the annual heating energy per m2 heated floor area [kWh/m2.a] for defrosting, based on a variable electric resistance heating.

QdefrtdefrΔΤdefrcairqnetpef,

where

tdefr is the duration of defrosting period, i.e. when the outdoor temperature is below – 4 °C [h/a], and

ΔΤdefr is the average difference in K between the outdoor temperature and – 4 °C during the defrosting period.

Qdefr applies only to bidirectional units with recuperative heat exchanger; for unidirectional units or units with regenerative heat exchanger is Qdefr = 0.

SPI and ηt are values derived from tests and calculation methods.

Other parameters and their defaults are given in Table 1.

[Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr * Δtdefr * cair * qnet * pef. For unidirectional units or unit with regenerative heat exchanger is Qdefr = 0]

general typology | MISC

Ducted units | 1,1

Non-ducted units | 1,21

ventilation control | CTRL

Manual control (no DCV) | 1

Clock control (no DCV) | 0,95

Central demand control | 0,85

Local demand control | 0,65

motor & drive | x-value

on/off & single speed | 1

2-speed | 1,2

multi-speed | 1,5

variable speed | 2

Climate |

th

in h

ΔΤh

in K

tdefr

in h

ΔΤdefr

in K

Qdefr

in kWh/a.m2

Cold | 6552 | 14,5 | 1003 | 5,2 | 5,82

Average | 5112 | 9,5 | 168 | 2,4 | 0,45

Warm | 4392 | 5 | — | — | —

Defaults | value

specific heat capacity of air, cair in kWh/(m3K) | 0,000344

net ventilation requirement per m2 heated floor area, qnet in m3/h.m2 | 1,3

reference natural ventilation rate per m2 heated floor area, qref in m3/h.m2 | 2,2

annual operating hours, ta in h | 8760

primary energy factor electric power generation & distribution, pef | 2,5

space heating efficiency, ηh | 75 %