The specific energy consumption SEC is calculated with the following equation:
SECtapefqnetMISCCTRLxSPIthΔΤhηh– 1cairqrefqnetCTRLMISC1ηtQdefr
where:
SEC is Specific Energy Consumption for ventilation per m2 heated floor area of a dwelling or building [kWh/(m2.a)];
ta is annual operating hours [h/a];
pef is primary energy factor for electric power generation and distribution [-];
qnet is net ventilation rate demand per m2 heated floor area [m3/h.m2];
MISC is an aggregated general typology factor, incorporating factors for ventilation effectiveness, duct leakage and extra infiltration [-];
CTRL is ventilation control factor [-];
x is an exponent that takes into account non-linearity between thermal energy and electricity saving, depending on motor and drive characteristics [-];
SPI is Specific Power Input [kW/(m3/h)];
th is total hours heating season [h];
ΔΤh is the average difference in indoor (19 °C) and outdoor temperature over a heating season, minus 3K correction for solar and internal gains [K];
ηh is the average space heating efficiency [-];
cair is the specific heat capacity of air at constant pressure and density [kWh/(m3 K)];
qref is the reference natural ventilation rate per m2 heated floor area [m3/h.m2];
ηt is the thermal efficiency of heat recovery [-];
Qdefr is the annual heating energy per m2 heated floor area [kWh/m2.a] for defrosting, based on a variable electric resistance heating.
QdefrtdefrΔΤdefrcairqnetpef,
where
tdefr is the duration of defrosting period, i.e. when the outdoor temperature is below – 4 °C [h/a], and
ΔΤdefr is the average difference in K between the outdoor temperature and – 4 °C during the defrosting period.
Qdefr applies only to bidirectional units with recuperative heat exchanger; for unidirectional units or units with regenerative heat exchanger is Qdefr = 0.
SPI and ηt are values derived from tests and calculation methods.
Other parameters and their defaults are given in Table 1.
[Defrosting applies only to bidirectional units with recuperative heat exchanger and is calculated as Qdefr = tdefr * Δtdefr * cair * qnet * pef. For unidirectional units or unit with regenerative heat exchanger is Qdefr = 0]
general typology | MISC
Ducted units | 1,1
Non-ducted units | 1,21
ventilation control | CTRL
Manual control (no DCV) | 1
Clock control (no DCV) | 0,95
Central demand control | 0,85
Local demand control | 0,65
motor & drive | x-value
on/off & single speed | 1
2-speed | 1,2
multi-speed | 1,5
variable speed | 2
Climate |
th
in h
ΔΤh
in K
tdefr
in h
ΔΤdefr
in K
Qdefr
in kWh/a.m2
Cold | 6552 | 14,5 | 1003 | 5,2 | 5,82
Average | 5112 | 9,5 | 168 | 2,4 | 0,45
Warm | 4392 | 5 | — | — | —
Defaults | value
specific heat capacity of air, cair in kWh/(m3K) | 0,000344
net ventilation requirement per m2 heated floor area, qnet in m3/h.m2 | 1,3
reference natural ventilation rate per m2 heated floor area, qref in m3/h.m2 | 2,2
annual operating hours, ta in h | 8760
primary energy factor electric power generation & distribution, pef | 2,5
space heating efficiency, ηh | 75 %