3 ANNEX III Specific ecodesign requirements for NRVUs, as referred to in Article 3(2) and 3(4), Commission Regulation (EU) No 1253/2014 of 7 July 2014 implementing Directive 2009/125/E…

In forcesince 7 Jul 2014
1.

From 1 January 2016:

All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive.

All BVUs shall have a HRS.

The HRS shall have a thermal by-pass facility.

The minimum thermal efficiency ηt_nrvu of all HRS except run-around HRS in BVUs shall be 67 % and the efficiency bonus E = (ηt_nrvu – 0,67) * 3000 if the thermal efficiency ηt_nrvu is at least 67 %, otherwise E = 0.

The minimum thermal efficiency ηt_nrvu of run-around HRS in BVUs shall be 63 % and the efficiency bonus E = (ηt_nrvu – 0,63) * 3000 if the thermal efficiency ηt_nrvu is at least 63 %, otherwise E = 0.

The minimum fan efficiency for UVUs (ηνu) is

6,2 % * ln(P) + 35,0 % if P ≤ 30 kW and

56,1 % if P > 30 kW.

The maximum internal specific fan power of ventilation components (SFPint_limit) in W/(m3/s) is

for a BVU with run-around HRS

1700 + E – 300 * qnom/2 – F if qnom < 2 m3/s and

1400 + E – F if qnom ≥ 2 m3/s;

for a BVU with other HRS

1200 + E – 300 * qnom/2 – F if qnom < 2 m3/s and

900 + E – F if qnom ≥ 2 m3/s;

250 for an UVU intended to be used with a filter.

2.

From 1 January 2018:

All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive.

All BVUs shall have a HRS.

The HRS shall have a thermal by-pass facility.

The minimum thermal efficiency ηt_nrvu of all HRS except run-around HRS in BVUs shall be 73 % and the efficiency bonus E = (ηt_nrvu – 0,73) * 3000 if the thermal efficiency ηt_nrvu is at least 73 %, otherwise E = 0.

The minimum thermal efficiency ηt_nrvu of run-around HRS in BVUs shall be 68 % and the efficiency bonus E = (ηt_nrvu – 0,68) * 3000 if the thermal efficiency ηt_nrvu is at least 68 %, otherwise E = 0.

The minimum fan efficiency for UVUs (ηνu) is

6,2 % * ln(P) + 42,0 % if P ≤ 30 kW and

63,1 % if P > 30 kW.

The maximum internal specific fan power of ventilation components (SFPint_limit) in W/(m3/s) is

for a BVU with run-around HRS

1600 + E – 300 * qnom/2 – F if qnom < 2 m3/s and

1300 + E – F if qnom ≥ 2 m3/s;

for a BVU with other HRS

1100 + E – 300 * qnom/2 – F if qnom < 2 m3/s and

800 + E – F if qnom ≥ 2 m3/s;

230 for an UVU intended to be used with a filter.

If a filter unit is part of the configuration the product shall be equipped with a visual signalling or an alarm in the control system which shall be activated if the filter pressure drop exceeds the maximum allowable final pressure drop.