From 1 January 2016:
All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive.
All BVUs shall have a HRS.
The HRS shall have a thermal by-pass facility.
The minimum thermal efficiency ηt_nrvu of all HRS except run-around HRS in BVUs shall be 67 % and the efficiency bonus E = (ηt_nrvu – 0,67) * 3000 if the thermal efficiency ηt_nrvu is at least 67 %, otherwise E = 0.
The minimum thermal efficiency ηt_nrvu of run-around HRS in BVUs shall be 63 % and the efficiency bonus E = (ηt_nrvu – 0,63) * 3000 if the thermal efficiency ηt_nrvu is at least 63 %, otherwise E = 0.
The minimum fan efficiency for UVUs (ηνu) is
6,2 % * ln(P) + 35,0 % if P ≤ 30 kW and
56,1 % if P > 30 kW.
The maximum internal specific fan power of ventilation components (SFPint_limit) in W/(m3/s) is
for a BVU with run-around HRS
1700 + E – 300 * qnom/2 – F if qnom < 2 m3/s and
1400 + E – F if qnom ≥ 2 m3/s;
for a BVU with other HRS
1200 + E – 300 * qnom/2 – F if qnom < 2 m3/s and
900 + E – F if qnom ≥ 2 m3/s;
250 for an UVU intended to be used with a filter.
From 1 January 2018:
All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive.
All BVUs shall have a HRS.
The HRS shall have a thermal by-pass facility.
The minimum thermal efficiency ηt_nrvu of all HRS except run-around HRS in BVUs shall be 73 % and the efficiency bonus E = (ηt_nrvu – 0,73) * 3000 if the thermal efficiency ηt_nrvu is at least 73 %, otherwise E = 0.
The minimum thermal efficiency ηt_nrvu of run-around HRS in BVUs shall be 68 % and the efficiency bonus E = (ηt_nrvu – 0,68) * 3000 if the thermal efficiency ηt_nrvu is at least 68 %, otherwise E = 0.
The minimum fan efficiency for UVUs (ηνu) is
6,2 % * ln(P) + 42,0 % if P ≤ 30 kW and
63,1 % if P > 30 kW.
The maximum internal specific fan power of ventilation components (SFPint_limit) in W/(m3/s) is
for a BVU with run-around HRS
1600 + E – 300 * qnom/2 – F if qnom < 2 m3/s and
1300 + E – F if qnom ≥ 2 m3/s;
for a BVU with other HRS
1100 + E – 300 * qnom/2 – F if qnom < 2 m3/s and
800 + E – F if qnom ≥ 2 m3/s;
230 for an UVU intended to be used with a filter.
If a filter unit is part of the configuration the product shall be equipped with a visual signalling or an alarm in the control system which shall be activated if the filter pressure drop exceeds the maximum allowable final pressure drop.