2 ANNEX II Specific ecodesign requirements for RVUs, as referred to in Article 3(1) and 3(3), Commission Regulation (EU) No 1253/2014 of 7 July 2014 implementing Directive 2009/125/E…

In forcesince 7 Jul 2014
1.

From 1 January 2016:

SEC, calculated for average climate, shall be no more than 0 kWh/(m2.a).

Non-ducted units including ventilation units intended to be equipped with one duct connection on either supply or extract air side shall have a maximum LWA of 45 dB.

All VUs, except dual use units, shall be equipped with a multi-speed drive or variable speed drive.

All BVUs shall have a thermal by-pass facility.

2.

From 1 January 2018:

SEC, calculated for average climate, shall be no more than – 20 kWh/(m2.a).

Non-ducted units including ventilation units intended to be equipped with one duct connection on either supply or extract air side shall have a maximum LWA of 40 dB.

All VUs, except dual use units, shall be equipped with a multi-speed drive or variable speed drive.

All BVUs shall have a thermal by-pass facility.

Ventilation units with a filter shall be equipped with a visual filter change warning signal.