4 Appendix C, Decision_act (EU) 2012/115

In forcesince 10 Feb 2012

Pollutant | Fuel type | ELV (mg/Nm3)

50-100 MW | > 100-300 MW | > 300-500 MW | > 500 MW

SO2 | Solid | 2000 | 2000 to 400 (linear scale) (Note 1) | 400

Liquid | 1700 |

1700 to 400

(linear scale)

400

Gaseous |

35 in general

5 for liquefied gas

800 for coke oven gas and blast furnace gas

NOx

(Note 6)

Solid

(Note 2)

600 |

200

(Note 3)

Liquid | 450 | 400

Gaseous | 300 | 200

Dust | Solid | 100 | 50 (Note 4)

Liquid | 50 (Note 5)

Gaseous |

5 in general

10 for blast furnace gas

50 for steel industry gases that can be used elsewhere

The reference oxygen content is 6 % for solid fuels and 3 % for liquid and gaseous fuels.

1.

800 mg/Nm3 for plants with a rated thermal input greater than or equal to 400 MW, which do not operate more than 1500 hours per year.

2.

1200 mg/Nm3 for plants that in the 12-month period ending on 1 January 2001 operated on, and continue to operate on, solid fuels whose volatile content is < 10 %.

3.

450 mg/Nm3 for plants which do not operate more than 1500 hours per year.

4.

100 mg/Nm3 for plants for which the original construction licence or, in the absence of such a procedure, the original operating licence was granted before 1 July 1987 and which are burning solid fuel with a heat content of less than 5800 kJ/kg, a moisture content > 45 % by weight, a combined moisture and ash content > 60 % by weight and a calcium oxide content > 10 %.

5.

100 mg/Nm3 for plants with a rated thermal input below 500 MW and burning liquid fuel with an ash content > 0,06 %.

6.

for plants located in the French Overseas Departments, the Azores, Madeira or the Canary Islands the following ELV apply: solid fuels in general: 650 mg/Nm3; solid fuels with < 10 % volatile compounds: 1300 mg/Nm3; liquid fuels: 450 mg/Nm3; gaseous fuels: 350 mg/Nm3.

ELV for NOx

(mg/Nm3)

Gas engines (firing gaseous fuels) | 100

Gas turbines (including CCGT) firing the following fuels:

Natural gas (Note 1) |

50

(Notes 2 and 3)

Gaseous fuels other than natural gas | 120

Light and middle distillates | 120

The reference oxygen content is 15 %.

1.

Naturally occurring methane with not more than 20 % (by volume) of inerts and other constituents.

2.

75 mg/Nm3 in the following cases (where the efficiency of the gas turbine is determined at ISO base load conditions):

gas turbines, used in combined heat and power systems having an overall efficiency greater than 75 %,

gas turbines used in combined cycle plants having an annual average overall electrical efficiency greater than 55 %,

gas turbines for mechanical drives.

3.

For single cycle gas turbines not falling into any of the categories mentioned under Note 2, but having an efficiency greater than 35 % (at ISO base load conditions), the ELV shall be 50 × η/35 where η is the gas turbine efficiency (at ISO base load conditions) expressed as a percentage.

Total rated thermal input | Minimum rate of desulphurisation

50-100 MW | 60 %

> 100-300 MW | 75 %

> 300-500 MW | 90 %

> 500 MW |

94 % in general

92 % for plants where a contract for the fitting of FGD or lime injection equipment has been entered into, and work on its installation has commenced, before 1 January 2001