Schedule 2 INDICATOR PARAMETERS, The Water Supply (Water Quality) Regulations 2010 (revoked)
The Water Supply (Water Quality) (Amendment) Regulations 201645Law
In the table in Schedule 2 to the 2010 Regulations, omit— (a) the entry in relation to total indicative dose (for radioactivity); (b) the entry in relation to tritium (for radioactivity); and (c) note (ii).
The Water Supply (Water Quality) (Amendment) Regulations 20112Law
… with the parameters E.coli, conductivity and hydrogen ion (item 2 in Table A in Schedule 1, and items 6 and 7 in Schedule 2, respectively), and the second and any subsequent samples must be analysed for compliance with those and every …
Changed on 15 Jun 2018
Notes:
1 The water should not be aggressive.
2 …
3 May be monitored from samples of water leaving treatment works or other supply point, as no significant change during distribution.
Item | Parameters | Specification Concentration or Value (maximum unless otherwise stated) or State | Units of Measurement | Point of compliance
1 | Ammonium | 0.50 | mgNH4/l | Consumers' taps
2 | Chloride 1 | 250 | mgCl/l | Supply point3
3 | Clostridium perfringens (including spores) | 0 | Number/100 ml | Supply point3
4 | Coliform bacteria | 0 | Number/100 ml | Consumers' taps
5 | Colony counts | No abnormal change | Number/1 ml at 22°C | Consumers' taps, service
Number/1 ml at 37°C | Reservoirs and treatment works
6 | Conductivity 1 | 2500 | μS/cm at 20°C | Supply point3
7 | Hydrogen ion | 9.5 | pHvalue | Consumers' taps
6.5 (minimum) | pH value |
8 | Sulphate 1 | 250 | mgSO4/l | Supply point3
9 | … | … | … | …
10 | Total organic carbon (TOC) | No abnormal change | mgC/l | Supply point3
11 | … | … | … | …
12 | Turbidity | 1 | NTU | Treatment works…
- 15 Jun 2018 – todayin force
- 14 Apr 2016 – 15 Jun 2018earlier wording
- 20 Apr 2010 – 14 Apr 2016earlier wording