Art. 99 Regulation (EU) 2017/1485

Final year-ahead availability plans

In forcesince 2 Aug 2017cited 2×
1.

Before 1 December of each calendar year, each TSO shall:

(a)

finalise the year-ahead outage coordination of internal relevant assets; and

(b)

finalise the year-ahead availability plans for internal relevant assets and store them on the ENTSO for Electricity operational planning data environment.

2.

Before 1 December of each calendar year, the TSO shall provide to its outage planning agent the final year-ahead availability plan of each internal relevant asset.

3.

Before 1 December of each calendar year, the TSO shall provide to the relevant DSO the final year-ahead availability plan for each internal relevant asset located in a distribution system.

4.

Before 1 December of each calendar year, the TSO shall provide to the relevant CDSO the final year-ahead availability plan for each internal relevant asset located in a closed distribution system.