Art. 71 Regulation (EU) 2017/1485

Quality control for grid models

In forcesince 2 Aug 2017

When defining the quality controls in accordance with Articles 67(1)(b) and 70(1)(c), all TSOs shall jointly determine controls aimed at least to check:

(a)

the coherence of the connection status of interconnectors;

(b)

that voltage values are within the usual operational values for those transmission system elements having influence on other control areas;

(c)

the coherence of transitory admissible overloads of interconnectors; and

(d)

that active power and reactive power injections or withdrawals are compatible with usual operational values.