Art. 30 Regulation (EU) 2016/1447

Power oscillation damping capability

In forcesince 26 Aug 2016cited 3×

The HVDC system shall be capable of contributing to the damping of power oscillations in connected AC networks. The control system of the HVDC system shall not reduce the damping of power oscillations. The relevant TSO shall specify a frequency range of oscillations that the control scheme shall positively damp and the network conditions when this occurs, at least accounting for any dynamic stability assessment studies undertaken by TSOs to identify the stability limits and potential stability problems in their transmission systems. The selection of the control parameter settings shall be agreed between the relevant TSO and the HVDC system owner.

  • Netcode elektriciteit6.18Law

    … tussen 0,1 Hz en 2,0 Hz door modulatie van werkzaam vermogen en blindvermogen actief te dempen, als bedoeld in artikel 30 van de Verordening (EU) 2016/1447 (NC HVDC). 2. De netbeheerder van het landelijk hoogspanningsnet legt de …

  • Systeemcode elektriciteit 20266.18Law

    … tussen 0,1 Hz en 2,0 Hz door modulatie van werkzaam vermogen en blindvermogen actief te dempen als bedoeld in artikel 30 van Verordening (EU) 2016/1447 (NC HVDC). 2. De transmissiesysteembeheerder legt de voorwaarden, die tot activering …

  • HVDC Anforderungs-V15Law

    § 15. (1) Ergänzend zu Art. 30 der Verordnung (EU) 2016/1447 wird für HGÜ-Systeme festgelegt, dass diese in der Lage sein müssen, Leistungspendelungen mindestens im Frequenzbereich 0,1 bis 2,0 Hz aktiv zu dämpfen. (2) Die erstmaligen …