ANNEX II, Regulation (EU) 2016/1388

In forcesince 17 Aug 2016

Synchronous area | Voltage range | Time period for operation

Continental Europe | 0,90 pu-1,118 pu | Unlimited

1,118 pu-1,15 pu | To be specified by each TSO but not less than 20 minutes and not more than 60 minutes

Nordic | 0,90 pu-1,05 pu | Unlimited

1,05 pu-1,10 pu | 60 minutes

Great Britain | 0,90 pu-1,10 pu | Unlimited

Ireland and Northern Ireland | 0,90 pu-1,118 pu | Unlimited

Baltic | 0,90 pu-1,118 pu | Unlimited

1,118 pu-1,15 pu | 20 minutes

The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network where the voltage base for pu values is at or above 110 kV and up to (not including) 300 kV.

Synchronous area | Voltage range | Time period for operation

Continental Europe | 0,90 pu-1,05 pu | Unlimited

1,05 pu-1,10 pu | To be specified by each TSO but not less than 20 minutes and not more than 60 minutes

Nordic | 0,90 pu-1,05 pu | Unlimited

1,05 pu-1,10 pu | To be specified by each TSO but not more than 60 minutes

Great Britain | 0,90 pu-1,05 pu | Unlimited

1,05 pu-1,10 pu | 15 minutes

Ireland and Northern Ireland | 0,90 pu-1,05 pu | Unlimited

Baltic | 0,90 pu-1,097 pu | Unlimited

1,097 pu-1,15 pu | 20 minutes

The table shows the minimum time periods during which a transmission-connected demand facility, a transmission-connected distribution facility or a transmission-connected distribution system has to be capable of operating for voltages deviating from the reference 1 pu value at the connection point without disconnecting from the network, where the voltage base for pu values is from 300 kV to 400 kV (including).