Synchronous area | Frequency range | Time period for operation
Continental Europe | 47,5 Hz-48,5 Hz | To be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 Hz | Unlimited
51,0 Hz-51,5 Hz | 30 minutes
Nordic | 47,5 Hz-48,5 Hz | 30 minutes
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 30 minutes
49,0 Hz-51,0 Hz | Unlimited
51,0 Hz-51,5 Hz | 30 minutes
Great Britain | 47,0 Hz-47,5 Hz | 20 seconds
47,5 Hz-48,5 Hz | 90 minutes
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 Hz | Unlimited
51,0 Hz-51,5 Hz | 90 minutes
51,5 Hz-52,0 Hz | 15 minutes
Ireland and Northern Ireland | 47,5 Hz-48,5 Hz | 90 minutes
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 90 minutes
49,0 Hz-51,0 Hz | Unlimited
51,0 Hz-51,5 Hz | 90 minutes
Baltic | 47,5 Hz-48,5 Hz | To be specified by each TSO, but not less than 30 minutes
48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz
49,0 Hz-51,0 Hz | Unlimited
51,0 Hz-51,5 Hz | To be specified by each TSO, but not less than 30 minutes
The table shows the minimum time periods for which a transmission-connected demand facility, a transmission-connected distribution facility or a distribution system has to be capable of operating on different frequencies, deviating from a nominal value, without disconnecting from the network.