ANNEX I, Regulation (EU) 2016/1388

In forcesince 17 Aug 2016

Synchronous area | Frequency range | Time period for operation

Continental Europe | 47,5 Hz-48,5 Hz | To be specified by each TSO, but not less than 30 minutes

48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz

49,0 Hz-51,0 Hz | Unlimited

51,0 Hz-51,5 Hz | 30 minutes

Nordic | 47,5 Hz-48,5 Hz | 30 minutes

48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 30 minutes

49,0 Hz-51,0 Hz | Unlimited

51,0 Hz-51,5 Hz | 30 minutes

Great Britain | 47,0 Hz-47,5 Hz | 20 seconds

47,5 Hz-48,5 Hz | 90 minutes

48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 90 minutes

49,0 Hz-51,0 Hz | Unlimited

51,0 Hz-51,5 Hz | 90 minutes

51,5 Hz-52,0 Hz | 15 minutes

Ireland and Northern Ireland | 47,5 Hz-48,5 Hz | 90 minutes

48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than 90 minutes

49,0 Hz-51,0 Hz | Unlimited

51,0 Hz-51,5 Hz | 90 minutes

Baltic | 47,5 Hz-48,5 Hz | To be specified by each TSO, but not less than 30 minutes

48,5 Hz-49,0 Hz | To be specified by each TSO, but not less than the period for 47,5 Hz-48,5 Hz

49,0 Hz-51,0 Hz | Unlimited

51,0 Hz-51,5 Hz | To be specified by each TSO, but not less than 30 minutes

The table shows the minimum time periods for which a transmission-connected demand facility, a transmission-connected distribution facility or a distribution system has to be capable of operating on different frequencies, deviating from a nominal value, without disconnecting from the network.