1.1. The information in the product fiche of the space heater shall be provided in the following order and shall be included in the product brochure or other literature provided with the product:
supplier’s name or trademark;
supplier’s model identifier;
the seasonal space heating energy efficiency class of the model, determined in accordance with point 1 of Annex II;
the rated heat output, including the rated heat output of any supplementary heater, in kW, rounded to the nearest integer (for heat pump space heaters under average climate conditions);
the seasonal space heating energy efficiency in %, rounded to the nearest integer and calculated in accordance with points 3 and 4 of Annex VII (for heat pump space heaters under average climate conditions);
the annual energy consumption in kWh in terms of final energy and/or in GJ in terms of GCV, rounded to the nearest integer and calculated in accordance with points 3 and 4 of Annex VII (for heat pump space heaters under average climate conditions);
the sound power level LWA, indoors, in dB, rounded to the nearest integer (for heat pump space heaters if applicable);
any specific precautions that shall be taken when the space heater is assembled, installed or maintained;
in addition, for cogeneration space heaters:
the electrical efficiency in %, rounded to the nearest integer;
in addition, for heat pump space heaters:
the rated heat output, including the rated heat output of any supplementary heater, in kW, under colder and warmer climate conditions, rounded to the nearest integer;
the seasonal space heating energy efficiency in %, under colder and warmer climate conditions, rounded to the nearest integer and calculated in accordance with point 4 of Annex VII;
the annual energy consumption in kWh in terms of final energy and/or in GJ in terms of GCV, under colder and warmer climate conditions, rounded to the nearest integer and calculated in accordance with point 4 of Annex VII;
the sound power level LWA, outdoors, in dB, rounded to the nearest integer.
1.2. One fiche may cover a number of space heater models supplied by the same supplier.
1.3. The information contained in the fiche may be given in the form of a copy of the label, either in colour or in black and white. Where this is the case, the information listed in point 1.1 not already displayed on the label shall also be provided.
2.1. The information in the product fiche of the combination heater shall be provided in the following order and shall be included in the product brochure or other literature provided with the product:
supplier’s name or trademark;
supplier’s model identifier;
for space heating, the medium-temperature application (and for heat pump combination heaters the low-temperature application, if applicable); for water heating, the declared load profile, expressed as the appropriate letter and typical usage in accordance with Table 15 of Annex VII;
the seasonal space heating energy efficiency class and the water heating energy efficiency class of the model, determined in accordance with points 1 and 2 of Annex II;
the rated heat output, including the rated heat output of any supplementary heater, in kW, rounded to the nearest integer (for heat pump combination heaters under average climate conditions);
for space heating, the annual energy consumption in kWh in terms of final energy and/or in GJ in terms of GCV, rounded to the nearest integer and calculated in accordance with points 3 and 4 of Annex VII (for heat pump combination heaters under average climate conditions); for water heating, the annual electricity consumption in kWh in terms of final energy and/or the annual fuel consumption in GJ in terms of GCV, rounded to the nearest integer and calculated in accordance with point 5 of Annex VII (for heat pump combination heaters under average climate conditions);
the seasonal space heating energy efficiency in %, rounded to the nearest integer and calculated in accordance with points 3 and 4 of Annex VII (for heat pump combination heaters under average climate conditions); the water heating energy efficiency in %, rounded to the nearest integer and calculated in accordance with point 5 of Annex VII (for heat pump combination heaters under average climate conditions);
the sound power level LWA, indoors, in dB, rounded to the nearest integer (for heat pump combination heaters if applicable);
if applicable, an indication that the combination heater is able to work only during off-peak hours;
any specific precautions that shall be taken when the combination heater is assembled, installed or maintained;
in addition, for heat pump combination heaters:
the rated heat output, including the rated heat output of any supplementary heater, in kW, under colder and warmer climate conditions, rounded to the nearest integer;
for space heating, the annual energy consumption in kWh in terms of final energy and/or in GJ in terms of GCV, under colder and warmer climate conditions, rounded to the nearest integer and calculated in accordance with point 4 of Annex VII; for water heating, the annual electricity consumption in kWh in terms of final energy and/or the annual fuel consumption in GJ in terms of GCV, under colder and warmer climate conditions, rounded to the nearest integer and calculated in accordance with point 5 of Annex VII;
the seasonal space heating energy efficiency in %, under colder and warmer climate conditions, rounded to the nearest integer and calculated in accordance with point 4 of Annex VII; the water heating energy efficiency in %, under colder and warmer climate conditions, rounded to the nearest integer and calculated in accordance with point 5 of Annex VII;
the sound power level LWA, outdoors, in dB, rounded to the nearest integer.
2.2. One fiche may cover a number of combination heater models supplied by the same supplier.
2.3. The information contained in the fiche may be given in the form of a copy of the label, either in colour or in black and white. Where this is the case, the information listed in point 2.1 not already displayed on the label shall also be provided.
3.1. The information in the product fiche of the temperature control shall be provided in the following order and shall be included in the product brochure or other literature provided with the product:
supplier’s name or trade mark;
supplier’s model identifier;
the class of the temperature control;
the contribution of the temperature control to seasonal space heating energy efficiency in %, rounded to one decimal place.
3.2. One fiche may cover a number of temperature control models supplied by the same supplier.
4.1. The information in the product fiche of the solar device shall be provided in the following order and shall be included in the product brochure or other literature provided with the product (for pumps in the collector loop if applicable):
supplier’s name or trade mark;
supplier’s model identifier;
the collector aperture area in m2, to two decimal places;
the collector efficiency in %, rounded to the nearest integer;
the energy efficiency class of the solar hot water storage tank, determined in accordance with point 3 of Annex II;
the standing loss of the solar hot water storage tank in W, rounded to the nearest integer;
the storage volume of the solar hot water storage tank in litres and m3;
the annual non-solar heat contribution Qnonsol in kWh in terms of primary energy for electricity and/or in kWh in terms of GCV for fuels, for the load profiles M, L, XL and XXL under average climate conditions, rounded to the nearest integer;
the pump power consumption in W, rounded to the nearest integer;
the standby power consumption in W, to two decimal places;
the annual auxiliary electricity consumption Qaux in kWh in terms of final energy, rounded to the nearest integer.
4.2. One fiche may cover a number of solar device models supplied by the same supplier.
The fiche for packages of space heater, temperature control and solar device shall contain the elements set out in Figure 1, Figure 2, Figure 3 and Figure 4, respectively, for evaluating the seasonal space heating energy efficiency of a package of space heater, temperature control and solar device, including the following information:
I: the value of the seasonal space heating energy efficiency of the preferential space heater, expressed in %;
II: the factor for weighting the heat output of preferential and supplementary heaters of a package as set out in Tables 5 and 6 of this Annex, respectively;
III: the value of the mathematical expression: 29411 Prated, whereby Prated is related to the preferential space heater;
IV: the value of the mathematical expression 11511 Prated, whereby Prated is related to the preferential space heater;
in addition, for preferential heat pump space heaters:
V: the value of the difference between the seasonal space heating energy efficiencies under average and colder climate conditions, expressed in %;
VI: the value of the difference between the seasonal space heating energy efficiencies under warmer and average climate conditions, expressed in %.
The fiche for packages of combination heater, temperature control and solar device shall contain the elements set out in points (a) and (b):
the elements set out in Figure 1 and Figure 3, respectively, for evaluating the seasonal space heating energy efficiency of a package of combination heater, temperature control and solar device, including the following information:
I: the value of the seasonal space heating energy efficiency of the preferential combination heater, expressed in %;
II: the factor for weighting the heat output of the preferential and supplementary heaters of a package as set out in Tables 5 and 6 of this Annex, respectively;
III: the value of the mathematical expression: 29411 Prated, whereby Prated is related to the preferential combination heater;
IV: the value of the mathematical expression 11511 Prated, whereby Prated is related to the preferential combination heater;
in addition, for preferential heat pump combination heaters:
V: the value of the difference between the seasonal space heating energy efficiencies under average and colder climate conditions, expressed in %;
VI: the value of the difference between the seasonal space heating energy efficiencies under warmer and average climate conditions, expressed in %;
the elements set out in Figure 5 for evaluating the water heating energy efficiency of a package of combination heater, temperature control and solar device, where the following information shall be included:
I: the value of the water heating energy efficiency of the combination heater, expressed in %;
II: the value of the mathematical expression 220 QrefQnonsol, where Qref is taken from Table 15 in Annex VII and Qnonsol from the product fiche of the solar device for the declared load profile M, L, XL or XXL of the combination heater;
III: the value of the mathematical expression Qaux 2,5220 Qref, expressed in %, where Qaux is taken from the product fiche of the solar device and Qref from Table 15 in Annex VII for the declared load profile M, L, XL or XXL.
[The intermediate values are calculated by linear interpolation between the two adjacent values.] [Prated is related to the preferential space heater or combination heater.]
PsupPrated Psup | II, package without hot water storage tank | II, package with hot water storage tank
0 | 0 | 0
0,1 | 0,30 | 0,37
0,2 | 0,55 | 0,70
0,3 | 0,75 | 0,85
0,4 | 0,85 | 0,94
0,5 | 0,95 | 0,98
0,6 | 0,98 | 1,00
≥ 0,7 | 1,00 | 1,00
[The intermediate values are calculated by linear interpolation between the two adjacent values.] [Prated is related to the preferential space heater or combination heater.]
PratedPrated Psup | II, package without hot water storage tank | II, package with hot water storage tank
0 | 1,00 | 1,00
0,1 | 0,70 | 0,63
0,2 | 0,45 | 0,30
0,3 | 0,25 | 0,15
0,4 | 0,15 | 0,06
0,5 | 0,05 | 0,02
0,6 | 0,02 | 0
≥ 0,7 | 0 | 0