In Schedule 1 (prescribed concentrations and values) to the 2006 Regulations—
in Part II (national requirements) of Table B (chemical parameters), omit the entries for—
item 3 (hydrogen ion);
item 6 (odour); and
item 9 (taste);
in Table C (indicator parameters)—
in the heading for column (3), after “maximum” insert “ unless otherwise stated ”;
after the entry for item 5 (colony count) insert—
5A. | Colour | Acceptable to consumers and no abnormal change |
;
after the entry for item 6 (conductivity) insert—
6A. | Hydrogen ion |
9.5
6.5 (minimum)
pH value
6B. | Odour | Acceptable to consumers and no abnormal change |
6C. | Radon (for radioactivity)(ii) | 100 | Bq/l
;
after the entry for item 7 (sulphate) insert—
7A. | Taste | Acceptable to consumers and no abnormal change |
;
after the entry for item 10 (tritium) insert—
10A. | Turbidity | Acceptable to consumers and no abnormal change |
;
in the entry for item 8 (total indicative dose), omit “(ii)” and “/year”; and
in the entry for item 10 (tritium), after “(for radioactivity)” insert “ (iii) ”; and
in the notes to Table C, for note (ii) substitute—
Remedial action is to be deemed justified on radiological protection grounds, without further consideration, where radon concentrations exceed 1,000 Bq/l.
If the concentration of tritium exceeds this value, an analysis of the presence of other artificial radionuclides must be also carried out by Scottish Water.
.