The Water Quality (Scotland) Regulations 2010, 14
The Public Water Supplies (Scotland) Regulations 201450Law
… Provisions) Order 2003 ; (b) regulation 37(1)(c) of the Private Water Supplies (Scotland) Regulations 2006 ; (c) regulations 7 to 14 of the Water Quality (Scotland) Regulations 2010 ; (d) paragraph 9 in Schedule 1 to the European Union …
Changed on 1 Jan 2015
(1) Schedule 3 to the 2001 Regulations is amended in accordance with paragraphs (2) to (4).
(2) For Table 2 substitute—
TABLE 2
ANNUAL SAMPLING FREQUENCIES: WATER SUPPLY ZONES
1 See regulation 6(2) and Table 1 in Schedule 3
2 Sampling for these parameters may be within water supply zones or at supply points as specified in Table 3, subject to note (ii) and (iii) below.
3 Where the population is not an exact multiple of 5,000, the population figure should be rounded up to the nearest multiple of 5,000.
4 Audit monitoring in water supply zones is required only where sodium hypochlorite is added after water has left the treatment works. In other circumstances, audit monitoring is required at supply points.
5 To monitor for total indicative dose (for radioactivity).
(1) Substances and parameters | (2) Estimated population of water supply zone | (3) Reduced | (4) Standard
Subject to check monitoring
E. coli | < 100 ≥ 100 | – – | 4
Coliform bacteria | 12 per 5,000
Residual disinfectant | population3
Aluminium1 | | |
Ammonium | | |
Clostridium | | |
Perfringens (including | | |
spores)21 | | |
Colony counts | < 100 | 1 | 2
Colour | 100-4,999 | 2 | 4
Conductivity2 | 5,000-9,999 | 6 | 12
Hydrogen ion | 10,000-29,999 | 12 | 24
Iron1 | 30,000-49,999 | 18 | 36
Manganese1 | 50,000-79,999 | 26 | 52
Nitrate1 | 80,000-100,000 | 38 | 76
Nitrite1 | | |
Odour | | |
Taste | | |
Turbidity | | |
Subject to audit monitoring
Antimony | < 100 | – | 1
Arsenic | 100-4,999 | – | 4
Benzene2 | 5,000-100,000 | – | 8
Benzo(a)pyrene | | |
Boron2 | | |
Bromate42 | | |
Cadmium | | |
Chromium | | |
Copper | | |
Cyanide2 | | |
1,2 dichloroethane2 | | |
Enterococci | | |
Fluoride2 | | |
Lead | | |
Mercury2 | | |
Nickel | | |
Pesticides2 | | |
PAH | | |
Selenium | | |
Sodium | | |
Trichloroethene/ | | |
Tetrachloroethene2 | | |
Tetrachloromethane2 | | |
THM | | |
Chloride2 | | |
Sulphate2 | | |
Total Organic Carbon2 | | |
Tritium2 | | |
Gross alpha52 | | |
Gross beta52 | | |
Notes: | | |
(3) For Table 3 substitute—
TABLE 3
ANNUAL SAMPLING FREQUENCIES: SUPPLY POINTS
1 Check monitoring is required only in respect of surface waters (see regulation 6(2) and Table 1 in Schedule 3), otherwise audit monitoring.
2 Audit monitoring at supply points is permitted only where sodium hypochlorite is not added after water has left the treatment works. In other circumstances, audit monitoring is required in water supply zones.
3 To monitor for total indicative dose (for radioactivity).
(1) Item | (2) Substances and parameters | (3) Volume of water supplied m3/d | (4) Reduced | (5) Standard
Subject to check monitoring
1. | Clostridium Perfringens (including spores)1 | < 20 | – | 2
20–999 | 2 | 4
2. | Conductivity | 1,000-1,999 | 6 | 12
2,000-5,999 | 12 | 24
6,000-9,999 | 18 | 36
10,000-15,999 | 26 | 52
16,000-32,999 | 52 | 104
33,000-49,999 | 78 | 156
50,000-67,999 | 104 | 208
68,000-84,999 | 130 | 260
85,000-101,999 | 156 | 312
102,000-119,999 | 183 | 365
120,000-241,999 | 365 | 730
242,000-484,999 | 730 | 1,460
485,000-728,999 | 1,095 | 2,190
Subject to audit monitoring
3. | Benzene | | |
4. | Boron | | |
5. | Bromate2 | | |
6. | Cyanide | | |
7. | 1,2 dichloroethane | < 20 | | 1
8. | Fluoride | 20-999 | | 4
9. | Mercury | 1,000-49,999 | | 8
10. | Pesticides | 50,00-89,999 | | 12
11. | Trichloroethene/Tetrachloroethene | 90,000-299,999 | | 24
12. | Tetrachloromethane | 300,000-649,999 | | 36
13. | Chloride | ≥ 650,000 | | 48
14. | Sulphate | | |
15. | Total organic carbon | | |
16. | Tritium | | |
17. | Gross alpha3 | | |
18. | Gross beta3 | | |
Notes: | | | |
(4) For Table 4 substitute—
TABLE 4
ANNUAL SAMPLING FREQUENCIES: WATER TREATMENT WORKS
1 Check monitoring at treatment works is required only when chloramination is practised. In other circumstances, audit monitoring is required.
(1) Item | (2) Substances and parameters | (3) Volume of water supplied m3/d | (4) Reduced | (5) Standard
Subject to check monitoring
1. | E. coli | < 20 | – | 4
2. | Coliform bacteria | 20–1,999 | 12 | 52
3. | Colony counts | 2,000–5,999 | 52 | 104
4. | Residual disinfectant | 6,000–11,999 | 104 | 208
≥12,000 | 104 | 365
5. | Nitrite1 | < 20 | – | 2
6. | Turbidity | 20-999 | 2 | 4
1,000-1,999 | 6 | 12
2,000-5,999 | 12 | 24
6,000-9,999 | 18 | 36
10,000-15,999 | 26 | 52
16,000-32,999 | 52 | 104
33,000-49,999 | 78 | 156
50,000-67,999 | 104 | 208
68,000-84,999 | 130 | 260
85,000-101,999 | 156 | 312
102,000-119,999 | 183 | 365
120,000-241,999 | 365 | 730
242,000-484,999 | 730 | 1,460
485,000-728,999 | 1,095 | 2,190
Subject to audit monitoring
7. | Nitrite1 | < 20 | | 1
20–999 | | 4
1,000–49,999 | | 8
50,000–89,999 | | 12
90,000–299,999 | | 24
300,000–649,999 | | 36
≥650,000 | | 48
Notes: | | | |…
- 1 Jan 2015 – todayin force
- 20 Apr 2010 – 1 Jan 2015earlier wording