The automatic scheme against voltage collapse of the system defence plan may include one or more of the following schemes, depending on the results of a TSO's assessment of system security:
a scheme for low voltage demand disconnection according to Article 19(2) of Regulation (EU) 2016/1388;
a blocking scheme for on load tap changer according to Article 19(3) of Regulation (EU) 2016/1388; and
system protection schemes for voltage management.
Unless the assessment pursuant to paragraph 1 demonstrates that implementing a blocking scheme for on load tap changer is not necessary to prevent a voltage collapse in the TSO control area, the TSO shall establish the conditions under which the on load tap changer shall block according to Article 19(3) of Regulation (EU) 2016/1388, including at least:
the blocking method (local or remote from control room);
the voltage level threshold at the connection point;
the flow direction of reactive power; and
the maximum lapse of time between the detection of the threshold and the blocking.