Seasonal space heating energy efficiency of air heating products:
From 1 January 2018, the seasonal space heating energy efficiency of air heating products shall not fall below the values in Table 1:
[To be declared in the relevant tables in this Annex and in the technical documentation rounded to one decimal place.]
ηs,h
Warm air heaters using fuels except B1 warm air heaters with a rated heat output below 10 kW and except C2 and C4 warm air heaters with a rated heat output below 15 kW | 72
B1 warm air heaters with a rated heat output below 10 kW and C2 and C4 warm air heaters with a rated heat output below 15 kW | 68
Warm air heaters using electricity | 30
Air-to-air heat pumps, driven by an electric motor, except rooftop heat pumps | 133
Rooftop heat pumps | 115
Air-to-air heat pumps, driven by an internal combustion engine | 120
For multi-split heat pumps, the manufacturer shall establish conformity with this regulation based on measurements and calculations according to Annex III. For each model of outdoor side unit, a list of recommended combinations with compatible indoor side units shall be included in the technical documentation. The declaration of conformity shall then apply to all combinations mentioned in this list. The list of recommended combinations shall be made available prior to the purchase/lease/hire of an outdoor side unit.
From 1 January 2021, the seasonal space heating energy efficiency of air heating products shall not fall below the values in Table 2:
[To be declared in the relevant tables in this Annex and in the technical documentation rounded to one decimal place.]
ηs,h
Warm air heaters using fuels except B1 warm air heaters with a rated heat output below 10 kW and except C2 and C4 warm air heaters with a rated heat output below 15 kW | 78
Warm air heaters using electricity | 31
Air-to-air heat pumps, driven by an electric motor, except rooftop heat pumps | 137
Rooftop heat pumps | 125
Air-to-air heat pumps, driven by an internal combustion engine | 130
For multi-split heat pumps the manufacturer shall establish conformity with this regulation based on measurements and calculations according to Annex III. For each model of outdoor side unit, a list of recommended combinations with compatible indoor side units shall be included in the technical documentation. The declaration of conformity shall then apply to all combinations mentioned in this list. The list of recommended combinations shall be made available prior to the purchase/lease/hire of an outdoor side unit.
Seasonal space cooling energy efficiency of cooling products:
From 1 January 2018, the seasonal space cooling energy efficiency of cooling products shall not fall below the values in Table 3:
[To be declared in the relevant tables in this Annex and in the technical documentation rounded to one decimal place.]
ηs,c
Air-to-water chillers with rated cooling capacity < 400 kW, when driven by an electric motor | 149
Air-to-water chillers with rated cooling capacity ≥ 400 kW when driven by an electric motor | 161
Water/brine to-water chillers with rated cooling capacity < 400 kW when driven by an electric motor | 196
Water/brine to-water chillers with ≥ 400 kW rated cooling capacity < 1500 kW when driven by an electric motor | 227
Water/brine to-water chillers with rated cooling capacity ≥ 1500 kW when driven by an electric motor | 245
Air-to-water comfort chillers, when driven by an internal combustion engine | 144
Air-to-air air conditioners, driven by an electric motor, except rooftop air conditioners | 181
Rooftop air conditioners | 117
Air-to-air air conditioners, driven by an internal combustion engine | 157
For multi-split air conditioners the manufacturer shall establish conformity with this regulation based on measurements and calculations according to Annex III. For each model of outdoor side unit, a list of recommended combinations with compatible indoor side units shall be included in the technical documentation. The declaration of conformity shall then apply to all combinations mentioned in this list. The list of recommended combinations shall be made available prior to the purchase/lease/hire of an outdoor side unit.
From 1 January 2021, the seasonal space cooling energy efficiency of cooling products shall not fall below the values in Table 4:
[To be declared in the relevant tables in this Annex and in the technical documentation rounded to one decimal place.]
ηs,c
Air-to-water chillers with rated cooling capacity < 400 kW, when driven by an electric motor | 161
Air-to-water chillers with rated cooling capacity ≥ 400 kW when driven by an electric motor | 179
Water/brine to-water chillers with rated cooling capacity < 400 kW when driven by an electric motor | 200
Water/brine to-water chillers with ≥ 400 kW rated cooling capacity < 1500 kW when driven by an electric motor | 252
Water/brine to-water chillers with rated cooling capacity ≥ 1500 kW when driven by an electric motor | 272
Air-to-water chillers with rated cooling capacity ≥ 400 kW, when driven by an internal combustion engine | 154
Air-to-air air conditioners, driven by an electric motor, except rooftop air conditioners | 189
Rooftop air conditioners | 138
Air-to-air air conditioners, driven by an internal combustion engine | 167
For multi-split air conditioners the manufacturer shall establish conformity with this regulation based on measurements and calculations according to Annex III. For each model of outdoor side unit, a list of recommended combinations with compatible indoor side units shall be included in the technical documentation. The declaration of conformity shall then apply to all combinations mentioned in this list. The list of recommended combinations shall be made available prior to the purchase/lease/hire of an outdoor side unit.
Seasonal energy performance ratio of high temperature process chillers:
From 1 January 2018, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 5:
[To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.]
Heat transfer medium at the condensing side | Rated refrigeration capacity | Minimum SEPR value
Air | PA < 400 kW | 4,5
PA ≥ 400 kW | 5,0
Water | PA < 400 kW | 6,5
400 kW ≤ PA < 1500 kW | 7,5
PA ≥ 1500 kW | 8,0
From 1 January 2021, the seasonal energy performance ratio of high temperature process chillers shall not fall below the values in Table 6:
[To be declared in the relevant tables in this Annex and in the technical documentation rounded to two decimal places.]
Heat transfer medium at the condensing side | Rated refrigeration capacity | Minimum SEPR value
Air | PA < 400 kW | 5,0
PA ≥ 400 kW | 5,5
Water | PA < 400 kW | 7,0
400 kW ≤ PA < 1500 kW | 8,0
PA ≥ 1500 kW | 8,5
Emissions of nitrogen oxides:
From 26 September 2018, the emissions of nitrogen oxides, expressed in nitrogen dioxide, of warm air heaters, heat pumps, comfort chillers and air conditioners shall not exceed values in Table 7:
Warm air heaters using gaseous fuels | 100
Warm air heaters using liquid fuels | 180
Heat pumps, comfort chillers and air conditioners, equipped with external combustion engines using gaseous fuels | 70
Heat pumps, comfort chillers and air conditioners, equipped with external combustion engines using liquid fuels | 120
Heat pumps, comfort chillers and air conditioners, equipped with internal combustion engines using gaseous fuels | 240
Heat pumps, comfort chillers and air conditioners, equipped with internal combustion engines using liquid fuels | 420
From 1 January 2021, the emissions of nitrogen oxides, expressed in nitrogen dioxide, of warm air heaters shall not exceed values in Table 8:
Warm air heaters using gaseous fuels | 70
Warm air heaters using liquid fuels | 150
Product information:
From 1 January 2018, the instruction manuals for installers and end-users, and free access websites of manufacturers, their authorised representatives and importers shall provide the following product information:
for warm air heaters, the information set out in Table 9 of this Annex, measured and calculated in accordance with Annex III;
for comfort chillers, the information set out in Table 10 of this Annex, measured and calculated in accordance with Annex III;
for air-to-air air conditioners, the information set out in Table 11 of this Annex, measured and calculated in accordance with Annex III;
for water/brine-to-air air conditioners, the information set out in Table 12 of this Annex, measured and calculated in accordance with Annex III;
for fan coil units, the information set out in Table 13 of this Annex, measured and calculated in accordance with Annex III;
for heat pumps, the information set out in Table 14 of this Annex, measured and calculated in accordance with Annex III;
for high temperature process chillers, the information set out in Table 15 of this Annex, measured and calculated in accordance with Annex III;
any specific precautions that must be taken when the product is assembled, installed or maintained;
for heat generators or cold generators designed for air heating or cooling products, and air heating or cooling product housings to be equipped with such heat or cold generators, their characteristics, the requirements for assembly, to ensure compliance with the ecodesign requirements for air heating or cooling products and, where appropriate, the list of combinations recommended by the manufacturer;
for multi-split heat pumps and multi-split air conditioners, a list of appropriate indoor units;
for B1, C2 and C4 warm air heaters the following standard text: ‘This warm air heater is intended to be connected only to a flue shared between multiple dwellings in existing buildings. Due to a lower efficiency, any other use of this warm air heater shall be avoided and would result in higher energy consumption and higher operating costs’.
From 1 January 2018, the instruction manuals for installers and end-users, and a part for professionals of the free-access websites of manufacturers, their authorised representatives and importers shall provide the following product information:
information relevant for disassembly, recycling and/or disposal at end-of-life.
The technical documentation for the purposes of conformity assessment pursuant to Article 4 shall contain the following elements:
the elements specified in point (a);
where the information relating to a specific model has been obtained by calculation on the basis of design, and/or extrapolation from other combinations, the technical documentation shall include details of such calculations and/or extrapolations, and of tests undertaken to verify the accuracy of the calculations undertaken, including details of the mathematical model for calculating performance of such combinations, and of measurements taken to verify this model, and a list of any other models where the information included in the technical documentation was obtained on the same basis.
The manufacturer, their authorised representatives and importers of comfort chillers, air-to-air and water/brine-to-air air conditioners, heat pumps and high temperature process chillers shall provide laboratories performing market surveillance checks, upon request, the necessary information on the setting of the unit, as applied for the establishment of declared capacities, SEER/EER, SCOP/COP, SEPR/COP values, where applicable, and provide contact information for obtaining such information.
[Not required for electric warm air heaters.] [From 26 September 2018.]
Model(s): Information to identify the model(s) to which the information relates:
B1 warm air heater: [yes/no]
C2 warm air heater: [yes/no]
C4 warm air heater: [yes/no]
Type of fuel: [gas/liquid/electricity]
Item | Symbol | Value | Unit | | Item | Symbol | Value | Unit
Capacity | | Useful efficiency
Rated heating capacity | Pated,h | x,x | kW | | Useful efficiency at rated heating capacity | ηnom | x,x | %
Minimum capacity | Pmin | x,x | kW | | Useful efficiency at minimum capacity | ηpl | x,x | %
Electric power consumption | | Other items
At rated heating capacity | elmax | x,xxx | kW | | Envelope loss factor | Fenv | x,x | %
At minimal capacity | elmin | x,xxx | kW | | Ignition burner power consumption | Pign | x,x | kW
In standby mode | elsb | x,xxx | kW | | Emissions of nitrogen oxides | NOx | x | mg/kWh input energy (GCV)
Emission efficiency | ηs,flow | x,x | %
Seasonal space heating energy efficiency | ηs,h | x,x | %
Contact details | Name and address of the manufacturer or of its authorised representative.
[If Cdc is not determined by measurement then the default degradation coefficient of chillers shall be 0,9.] [From 26 September 2018.]
Model(s): Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of chiller: [select which: air or water/brine]
Indoor side heat exchanger chiller: [default: water]
Type: compressor driven vapour compression or sorption process
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
Item | Symbol | Value | Unit | | Item | Symbol | Value | Unit
Rated cooling capacity | Prated,c | x,x | kW | | Seasonal space cooling energy efficiency | ηs,c | x,x | %
Declared cooling capacity for part load at given outdoor temperatures Tj | | Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj = + 35 °C | Pdc | x,x | kW | | Tj = + 35 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 30 °C | Pdc | x,x | kW | | Tj = + 30 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 25 °C | Pdc | x,x | kW | | Tj = + 25 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 20 °C | Pdc | x,x | kW | | Tj = + 20 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Degradation co-efficient for chillers | Cdc | x,x | — | | | | |
Power consumption in modes other than ‘active mode’
Off mode | POFF | x,xxx | kW | | Crankcase heater mode | PCK | x,xxx | kW
Thermostat-off mode | PTO | x,xxx | kW | | Standby mode | PSB | x,xxx | kW
Other items
Capacity control | fixed/staged/variable | | For air-to-water comfort chillers: air flow rate, outdoor measured | — | x | m3/h
Sound power level, outdoor | LWA | x,x/x,x | dB | | For water/brine-to-water chillers: Rated brine or water flow rate, outdoor side heat exchanger | — | x | m3/h
Emissions of nitrogen oxides (if applicable) | NOx | x | mg/kWh input GCV |
GWP of the refrigerant | | | kg CO2 eq (100 years) | | | | |
Standard rating conditions used: [low temperature application/medium temperature application]
Contact details | Name and address of the manufacturer or of its authorised representative.
[If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.] [From 26 September 2018.]
Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Model(s): Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of air conditioner: [default: air]
Indoor side heat exchanger of air conditioner: [default: air]
Type: compressor driven vapour compression or sorption process
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
Item | Symbol | Value | Unit | | Item | Symbol | Value | Unit
Rated cooling capacity | Prated,c | x,x | kW | | Seasonal space cooling energy efficiency | ηs,c | x,x | %
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27°/19 °C (dry/wet bulb) | | Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj = + 35 °C | Pdc | x,x | kW | | Tj = + 35 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 30 °C | Pdc | x,x | kW | | Tj = + 30 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 25 °C | Pdc | x,x | kW | | Tj = + 25 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 20 °C | Pdc | x,x | kW | | Tj = + 20 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Degradation co-efficient for air conditioners | Cdc | x,x | — | | | | |
Power consumption in modes other than ‘active mode’
Off mode | POFF | x,xxx | kW | | Crankcase heater mode | PCK | x,xxx | kW
Thermostat-off mode | PTO | x,xxx | kW | | Standby mode | PSB | x,xxx | kW
Other items
Capacity control | fixed/staged/variable | | For air-to-air air conditioner: air flow rate, outdoor measured | — | x | m3/h
Sound power level, outdoor | LWA | x,x/x,x | dB | | | | |
If engine driven: Emissions of nitrogen oxides | NOx | x | mg/kWh fuel input GCV |
GWP of the refrigerant | | | kg CO2 eq (100 years) | | | | |
Contact details | Name and address of the manufacturer or of its authorised representative.
[If Cdc is not determined by measurement then the default degradation coefficient air conditioners shall be 0,25.] [From 26 September 2018. Where information relates to multi-split air conditioners, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.]
Model(s): Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of air conditioner: [default: water/brine]
Indoor side heat exchanger of air conditioner: [default: air]
Type: compressor driven vapour compression or sorption process
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
Item | Symbol | Value | Unit | | Item | Symbol | Value | Unit
Rated cooling capacity | Prated,c | x,x | kW | | Seasonal space cooling energy efficiency | ηs,c | x,x | %
Declared cooling capacity for part load at given outdoor temperatures Tj and indoor 27°/19 °C (dry/wet bulb) | | Declared energy efficiency ratio or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Outdoor temperature Tj | cooling tower (inlet/outlet) | ground coupled | | | | | | | |
Tj = + 35 °C | 30/35 | 10/15 | Pdc | x,x | kW | | Tj = + 35 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 30 °C | 26/* | 10/* | Pdc | x,x | kW | | Tj = + 30 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 25 °C | 22/* | 10/* | Pdc | x,x | kW | | Tj = + 25 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Tj = + 20 °C | 18/* | 10/* | Pdc | x,x | kW | | Tj = + 20 °C | EERd or GUEc,bin/AEFc,bin | x,x | %
Degradation co-efficient for air conditioners | Cdc | x,x | — | | | | |
Power consumption in modes other than ‘active mode’
Off mode | POFF | x,xxx | kW | | Crankcase heater mode | PCK | x,xxx | kW
Thermostat-off mode | PTO | x,xxx | kW | | Standby mode | PSB | x,xxx | kW
Other items
Capacity control | fixed/staged/variable | | | | |
Sound power level, outdoor | LWA | x,x/x,x | dB | | For water/brine-to-air air conditioners: Rated brine or water flow rate, outdoor side heat exchanger | — | x | m3/h
If engine driven
Emissions of nitrogen oxides (if applicable)
NOx | x | mg/kWh fuel input GCV |
GWP of the refrigerant | | | kg CO2 eq (100 years) | | | | |
Contact details | Name and address of the manufacturer or of its authorised representative.
Information to identify the model(s) to which the information relates:
Item | Symbol | Value | Unit | | Item | Symbol | Value | Unit
Cooling capacity (sensible) | Prated,c | x,x | kW | | Total electric power input | Pelec | x,xxx | kW
Cooling capacity (latent) | Prated,c | x,x | kW | | Sound power level (per speed setting, if applicable) | LWA | x,x/etc. | dB
Heating capacity | Prated,h | x,x | kW | | | | |
Contact details | Name and address of the manufacturer or of its authorised representative.
(*)
[If Cdh is not determined by measurement then the default degradation coefficient of heat pumps shall be 0,25.] [From 26 September 2018.]
Where information relates to multi-split heat pumps, the test result and performance data may be obtained on the basis of the performance of the outdoor unit, with a combination of indoor unit(s) recommended by the manufacturer or importer.
Information to identify the model(s) to which the information relates:
Outdoor side heat exchanger of heat pump: [select which: air/water/brine]
Indoor side heat exchanger of heat pump: [select which: air/water/brine]
Indication if the heater is equipped with a supplementary heater: yes/no
If applicable: driver of compressor: [electric motor or fuel driven, gaseous or liquid fuel, internal or external combustion engine]
Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons are optional.
Item | Symbol | Value | Unit | | Item | Symbol | Value | Unit
Rated heating capacity | Prated,h | x,x | kW | | Seasonal space heating energy efficiency | ηs,h | x,x | %
Declared heating capacity for part load at indoor temperature 20 °C and outdoor temperature Tj | | Declared coefficient of performance or gas utilisation efficiency/auxiliary energy factor for part load at given outdoor temperatures Tj
Tj = – 7 °C | Pdh | x,x | kW | | Tj = – 7 °C | COPd or GUEh,bin/AEFh,bin | x,x | %
Tj = + 2 °C | Pdh | x,x | kW | | Tj = + 2 °C | COPd or GUEh,bin/AEFh,bin | x,x | %
Tj = + 7 °C | Pdh | x,x | kW | | Tj = + 7 °C | COPd or GUEh,bin/AEFh,bin | x,x | %
Tj = + 12 °C | Pdh | x,x | kW | | Tj = + 12 °C | COPd or GUEh,bin/AEFh,bin | x,x | %
Tbiv = bivalent temperature | Pdh | x,x | kW | | Tbiv = bivalent temperature | COPd or GUEh,bin/AEFh,bin | x,x | %
TOL = operation limit | Pdh | x,x | kW | | TOL = operation limit | COPd or GUEh,bin/AEFh,bin | x,x | %
For air-to-water heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | Pdh | x,x | kW | | For water-to-air heat pumps: Tj = – 15 °C (if TOL < – 20 °C) | COPd or GUEh,bin/AEFh,bin | x,x | %
Bivalent temperature | Tbiv | x | °C | | For water-to-air heat pumps: Operation limit temperature | Tol | x | °C
Degradation co-efficient heat pumps | Cdh | x,x | — | | | | |
Power consumption in modes other than ‘active mode’ | | Supplementary heater
Off mode | POFF | x,xxx | kW | | Back-up heating capacity (*) | elbu | x,x | kW
Thermostat-off mode | PTO | x,xxx | kW | | Type of energy input |
Crankcase heater mode | PCK | x,xxx | kW | | Standby mode | PSB | x,xxx | kW
Other items