Art. 41 Regulation (EU) 2016/1447

Control requirements

In forcesince 26 Aug 2016
1.

During the synchronisation of a DC-connected power park module to the AC collection network, the DC-connected power park module shall have the capability to limit any voltage changes to a steady-state level specified by the relevant system operator, in coordination with the relevant TSO. The level specified shall not exceed 5 per cent of the pre-synchronisation voltage. The relevant system operator, in coordination with the relevant TSO, shall specify the maximum magnitude, duration and measurement window of the voltage transients.

2.

The DC-connected power park module owner shall provide output signals as specified by the relevant system operator, in coordination with the relevant TSO.