Taking into account the capabilities of the HVDC system specified in accordance with this Regulation, the relevant TSO shall determine whether active power contribution or reactive power contribution shall have priority during low or high voltage operation and during faults for which fault-ride-through capability is required. If priority is given to active power contribution, its provision shall be established within a time from the fault inception as specified by relevant TSO.
Art. 23 Regulation (EU) 2016/1447
Priority to active or reactive power contribution
In forcesince 26 Aug 2016cited 3×
… bij lage of hoge spanning en bij storingen waarvoor fault-ride-through-capaciteit vereist is, als bedoeld in artikel 23 van de Verordening (EU) 2016/1447 (NC HVDC).
Systeemcode elektriciteit 20266.12Law
… bij lage of hoge spanning en bij storingen waarvoor fault-ride-through-capaciteit vereist is als bedoeld in artikel 23 van Verordening (EU) 2016/1447 (NC HVDC).
§ 11. Ergänzend zu Art. 23 und Art. 40 Abs. 3 der Verordnung (EU) 2016/1447 wird festgelegt, dass bei Fehlern, die eine FRT-Fähigkeit erfordern, der Blindleistungsbeitrag gegenüber dem Wirkleistungsbeitrag Vorrang erhält. Der …