Without prejudice to point (a) of Article 14(3) and point (a) of Article 16(3), an AC-connected offshore power park module shall be capable of staying connected to the network and operating within the ranges of the network voltage at the connection point, expressed by the voltage at the connection point related to reference 1 pu voltage, and for the time periods specified in Table 10.
Notwithstanding the provisions of paragraph 1, the relevant TSO in Spain may require AC-connected offshore power park modules to remain connected to the network in the voltage range between 1,05 pu and 1,0875 pu for an unlimited period.
Notwithstanding the provisions of paragraph 1, the relevant TSOs in the Baltic synchronous area may require AC-connected offshore power park modules to remain connected to the 400 kV network in the voltage range and for the time periods that apply to the Continental Europe synchronous area.
Table 10
[The voltage base for pu values is below 300 kV.] [The voltage base for pu values is from 300 kV to 400 kV.]
Synchronous area | Voltage range | Time period for operation
Continental Europe | 0,85 pu-0,90 pu | 60 minutes
0,9 pu-1,118 pu | Unlimited
1,118 pu-1,15 pu | To be specified by each TSO, but not less than 20 minutes and not more than 60 minutes
0,90 pu-1,05 pu | Unlimited
1,05 pu-1,10 pu | To be specified by each TSO, but not less than 20 minutes and not more than 60 minutes
Nordic | 0,90 pu-1,05 pu | Unlimited
1,05 pu-1,10 pu | 60 minutes
1,05 pu-1,10 pu | To be specified by each TSO, but not more than 60 minutes
Great Britain | 0,90 pu-1,10 pu | Unlimited
0,90 pu-1,05 pu | Unlimited
1,05 pu-1,10 pu | 15 minutes
Ireland and Northern Ireland | 0,90 pu-1,10 pu | Unlimited
Baltic | 0,85 pu-0,90 pu | 30 minutes
0,90 pu-1,118 pu | Unlimited
1,118 pu-1,15 pu | 20 minutes
0,88 pu-0,90 pu | 20 minutes
0,90 pu-1,097 pu | Unlimited
1,097 pu-1,15 pu | 20 minutes
The table shows the minimum period during which an AC-connected offshore power park module must be capable of operating over different voltage ranges deviating from the reference 1 pu value without disconnecting.
The voltage stability requirements specified respectively in points (b) and (c) of Article 20(2) as well as in Article 21(3) shall apply to any AC-connected offshore power park module.
The reactive power capability at maximum capacity specified in point (b) of Article 21(3) shall apply to AC-connected offshore power park modules, except for Table 9. Instead, the requirements of Table 11 shall apply.
Table 11
Parameters for Figure 8
[At the offshore connection point for configuration 1.] [At the offshore connection point for configuration 2.]
Synchronous area | Maximum range of Q/Pmax | Maximum range of steady-state voltage level in PU
Continental Europe | 0,75 | 0,225
Nordic | 0,95 | 0,150
Great Britain |
0
0,33
0,225
Ireland and Northern Ireland | 0,66 | 0,218
Baltic | 0,8 | 0,22