Art. 17 Regulation (EU) 2016/631

Requirements for type B synchronous power-generating modules

In forcesince 14 Apr 2016cited 1×
1.

Type B synchronous power-generating modules shall fulfil the requirements listed in Articles 13, except for Article 13(2)(b), and 14.

2.

Type B synchronous power-generating modules shall fulfil the following additional requirements relating to voltage stability:

(a)

with regard to reactive power capability, the relevant system operator shall have the right to specify the capability of a synchronous power-generating module to provide reactive power;

(b)

with regard to the voltage control system, a synchronous power-generating module shall be equipped with a permanent automatic excitation control system that can provide constant alternator terminal voltage at a selectable setpoint without instability over the entire operating range of the synchronous power-generating module.

3.

With regard to robustness, type B synchronous power-generating modules shall be capable of providing post-fault active power recovery. The relevant TSO shall specify the magnitude and time for active power recovery.

  • RfG Anforderungs-Verordnung13149Law

    § 13. (1) Ergänzend zu Art. 17 Abs. 2 lit. a und Art. 20 Abs. 2 lit. a der Verordnung (EU) 2016/631 wird für synchrone und nichtsynchrone Stromerzeugungsanlagen vom Typ B folgende Fähigkeit zur Abgabe von Blindleistung bei …