The communications of the Member States to the Commission and the other Member States provided for in Article 4 shall have the following content:
|
gross calorific value (GCV) in MJ/m3
minimum/maximum;
Wobbe index in MJ/m3
minimum/maximum.
| Gas composition by volume in % of the total content:
C1 to C5 content in % (sum)
minimum/maximum;
N2 + CO2 content in %
minimum/maximum;
CO content in %
minimum/maximum;
unsaturated HC content in %
minimum/maximum;
hydrogen content in %
minimum/maximum.
| Information on toxic components contained in the gaseous fuel.
That communication shall also include either of the following:
| supply pressure at the inlet of appliances in mbar: | nominal/minimum/maximum;
|
supply pressure at the point of delivery in mbar:
nominal/minimum/maximum;
admissible pressure loss in the end-user gas installation in mbar:
nominal/minimum/maximum.
The reference conditions for Wobbe index and gross calorific value shall be the following:
| combustion reference temperature: | 15 °C;
| volume measurement reference temperature: | 15 °C;
| volume measurement reference pressure: | 1013,25 mbar.