For the purposes of compliance and verification of compliance with the requirements of this Regulation, measurements and calculations shall be made using harmonised standards the reference numbers of which have been published in the Official Journal of European Union, or other reliable, accurate and reproducible method, which takes into account the generally recognised state of the art methods, and whose results are deemed to be of low uncertainty. They shall fulfil all of the following technical parameters.
The determination of the seasonal energy consumption and efficiency for seasonal energy efficiency ratio (SEER) and seasonal coefficient of performance (SCOP) shall take into account:
European cooling and heating season(s), as defined in Table 1 below;
reference design conditions, as defined in Table 3 below;
electric energy consumption for all relevant modes of operation, using time periods as defined in Table 4 below;
effects of the degradation of the energy efficiency caused by on/off cycling (if applicable) depending on the type of control of the cooling and/or heating capacity;
corrections on the seasonal coefficients of performance in conditions where the heating load can not be met by the heating capacity;
the contribution of a back-up heater (if applicable) in the calculation of the seasonal efficiency of a unit in heating mode.
Where the information relating to a specific model, being a combination of indoor and outdoor unit(s), has been obtained by calculation on the basis of design, and/or extrapolation from other combinations, the documentation should include details of such calculations and/or extrapolations, and of tests undertaken to verify the accuracy of the calculations undertaken (including details of the mathematical model for calculating performance of such combinations, and of measurements taken to verify this model).
The rated energy efficiency ratio (EERrated) and, when applicable, rated coefficient of performance (COPrated) for single and double duct air conditioners shall be established at the standard rating conditions as defined in Table 2 below.
The calculation of seasonal electricity consumption for cooling (and/or heating) shall take into account electric energy consumption of all relevant modes of operation, as defined in Table 3 below, using operational hours, as defined in Table 4 below.
The comfort fan efficiency shall be determined on the basis of the nominal air flow rate of the unit divided by the nominal electric power input of the unit.
COOLING SEASON
j
#
Tj
°C
db
hj
h/annum
1 | 17 | 205
2 | 18 | 227
3 | 19 | 225
4 | 20 | 225
5 | 21 | 216
6 | 22 | 215
7 | 23 | 218
8 | 24 | 197
9 | 25 | 178
10 | 26 | 158
11 | 27 | 137
12 | 28 | 109
13 | 29 | 88
14 | 30 | 63
15 | 31 | 39
16 | 32 | 31
17 | 33 | 24
18 | 34 | 17
19 | 35 | 13
20 | 36 | 9
21 | 37 | 4
22 | 38 | 3
23 | 39 | 1
24 | 40 | 0
Total h. | 2602
HEATING SEASON
j
#
Tj
°C
db
hj
h/annum
Average | Warmer | Colder
1 to 8 | – 30 to – 23 | 0 | 0 | 0
9 | –22 | 0 | 0 | 1
10 | –21 | 0 | 0 | 6
11 | –20 | 0 | 0 | 13
12 | –19 | 0 | 0 | 17
13 | –18 | 0 | 0 | 19
14 | –17 | 0 | 0 | 26
15 | –16 | 0 | 0 | 39
16 | –15 | 0 | 0 | 41
17 | –14 | 0 | 0 | 35
18 | –13 | 0 | 0 | 52
19 | –12 | 0 | 0 | 37
20 | –11 | 0 | 0 | 41
21 | –10 | 1 | 0 | 43
22 | –9 | 25 | 0 | 54
23 | –8 | 23 | 0 | 90
24 | –7 | 24 | 0 | 125
25 | –6 | 27 | 0 | 169
26 | –5 | 68 | 0 | 195
27 | –4 | 91 | 0 | 278
28 | –3 | 89 | 0 | 306
29 | –2 | 165 | 0 | 454
30 | –1 | 173 | 0 | 385
31 | 0 | 240 | 0 | 490
32 | 1 | 280 | 0 | 533
33 | 2 | 320 | 3 | 380
34 | 3 | 357 | 22 | 228
35 | 4 | 356 | 63 | 261
36 | 5 | 303 | 63 | 279
37 | 6 | 330 | 175 | 229
38 | 7 | 326 | 162 | 269
39 | 8 | 348 | 259 | 233
40 | 9 | 335 | 360 | 230
41 | 10 | 315 | 428 | 243
42 | 11 | 215 | 430 | 191
43 | 12 | 169 | 503 | 146
44 | 13 | 151 | 444 | 150
45 | 14 | 105 | 384 | 97
46 | 15 | 74 | 294 | 61
Total h. | 4910 | 3590 | 6446
[In case of single duct air conditioners the condenser (evaporator) when cooling (heating) is not supplied with outdoor air, but indoor air.]
Appliance | Function |
Indoor air temperature
(°C)
Outdoor air temperature
(°C)
air conditioners, excluding single duct air conditioners | cooling | 27 (19) | 35 (24)
heating | 20 (max. 15) | 7(6)
single duct air conditioner | cooling | 35 (24) | 35 (24)
heating | 20 (12) | 20 (12)
Function/season |
Indoor air temperature
(°C)
Outdoor air temperature
(°C)
Bivalent temperature
(°C)
Operating limit temperature
(°C)
Tin | Tdesignc/Tdesignh | Tbiv | Tol
cooling | 27 (19) | Tdesignc = 35 (24) | n.a. | n.a.
heating/Average | 20 (15) | Tdesignh = – 10 (– 11) | max. 2 | max. – 7
heating/Warmer | Tdesignh = 2 (1) | max. 7 | max. 2
heating/Colder | Tdesignh = – 22 (– 23) | max. – 7 | max. – 15
Type of appliance/functionality
(if applicable)
Unit | Heating season | On mode | Thermostat-off mode | Standby mode | Off mode | Crankcase heater mode
cooling: HCE
heating: HHE
HTO | HSB | HOFF | HCK
Air conditioners, except single and double duct air conditioner
Cooling mode, if appliance offers cooling only | h/annum | | 350 | 221 | 2142 | 5088 | 7760
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/annum | | 350 | 221 | 2142 | 0 | 2672
Heating mode | h/annum | Average | 1400 | 179 | 0 | 0 | 179
Warmer | 1400 | 755 | 0 | 0 | 755
Colder | 2100 | 131 | 0 | 0 | 131
Heating mode, if appliance offers heating only | h/annum | Average | 1400 | 179 | 0 | 3672 | 3851
Warmer | 1400 | 755 | 0 | 4345 | 4476
Colder | 2100 | 131 | 0 | 2189 | 2944
Double duct air conditioner
Cooling mode, if appliance offers cooling only | h/60 min | | 1 | n/a | n/a | n/a | n/a
Cooling and heating modes, if appliance offers both modes | Cooling mode | h/60 min | | 1 | n/a | n/a | n/a | n/a
Heating mode | h/60 min | | 1 | n/a | n/a | n/a | n/a
Heating mode, if appliance offers heating only | h/60 min | | 1 | n/a | n/a | n/a | n/a
Single duct air conditioner
Cooling mode | h/60 min | | 1 | n/a | n/a | n/a | n/a
Heating mode | h/60 min | | 1 | n/a | n/a | n/a | n/a