ANNEX IV, Commission Regulation (EU) No 327/2011 of 30 March 2011 implementing Directive 2009/125/…

In forcesince 30 Mar 2011

At the time of adoption of this Regulation, the best available technology on the market for fans is as indicated in Table 1. These benchmarks may not always be achievable in all applications or for the full power range covered by the Regulation.

Fan types | Measurement category (A-D) |

Efficiency category

(static or total)

Efficiency grade

Axial fan | A, C | static | 65

B, D | total | 75

Centrifugal forward curved fan and centrifugal radial bladed fan | A, C | static | 62

B, D | total | 65

Centrifugal backward curved fan without housing | A, C | static | 70

Centrifugal backward curved fan with housing | A, C | static | 72

B, D | total | 75

Mixed flow fan | A, C | static | 61

B, D | total | 65

Cross flow fan | B, D | total | 32