Recital 10, Decision_act (EU) 2009/140

In forcesince 10 Feb 2009

Section 5.4 of standard EN 3-9:2006 states that the bursting disc safety device of the extinguisher must be activated when the pressure is between 10 % more than the maximum allowable pressure PS and the test pressure PT. The bursting disc is classified in the standard as a safety accessory. However, the bursting disc is not a typical pressure limiting device but rather a protection device, as it intends to limit damage in case of overfilling or overheating. Furthermore, point 2.11.2 of Annex I to Directive 97/23/EC on pressure limiting devices requires that these devices are so designed that the pressure will not permanently exceed the maximum allowable pressure PS and that only a short-duration surge may exceed PS and even then only 10 %. Therefore, this section can not confer the presumption of conformity to Directive 97/23/EC.