Boilers must comply with the following useful efficiency requirements:
at rated output, i.e. operating at rated output Pn expressed in kW, at an average boiler-water temperature of 70 oC, and
a part load, i.e. operating at 30 % part load, at an average boiler-water temperature which varies according to the type of the boiler.
The useful efficiency requirements to be complied with are set out in the following table:
[Including condensing boilers using liquid fuels.] [Temperature of boiler water-supply.]
Type of boiler | Range of power output | Efficiency at rated output | Efficiency at partload
kW | Average boiler-water temperature (in oC) | Efficiency requirement expressed (in %) | Average boiler-water temperature (in oC) | Efficiency requirement expressed (in %)
Standard boilers | 4 to 400 | 70 | ≥ 84 + 2 logPn | ≥ 50 | ≥ 80 + 3 logPn
Low-temperature boilers | 4 to 400 | 70 | ≥ 87,5 + 1,5 logPn | 40 | ≥ 87,5 + 1,5 logPn
Gas condensing boilers | 4 to 400 | 70 | ≥ 91 + 1 logPn | 30 | ≥ 97 + 1 logPn
The harmonized standards relating to the requirements of this Directive drawn up under mandate from the Commission in accordance with Directive 83/189/EEC and 88/182/EEC [OJ No L 81, 26.3.1988, p. 75.] shall determine, inter alia, the verification methods valid for production and measurements. Appropriate tolerances must be incorporated in the efficiency levels.