, The Private Water Supplies (Wales) Regulations 2017

In forcesince 20 Nov 2017

Table 1

Prescribed methods of analysis for microbiological parameters

Parameter | Method

Escherichia coli (E. coli) | EN ISO 9308-1 or EN ISO 9308-2

Enterococci | EN ISO 7899-2

Pseudomonas aeruginosa | EN-ISO 16266

Colony count 22°C — enumeration of culturable microorganisms | EN ISO 6222

Colony count 36°C — enumeration of culturable microorganisms | EN ISO 6222

Clostridium perfringens (including spores) | EN ISO 14189

Table 2

Prescribed performance characteristics for methods of analysis for chemical and indicator parameters: trueness, precision and limit of detection (on or before 31 December 2019)

Parameter |

Trueness % of prescribed

concentration or value or specification

(except for pH)

Precision % of prescribed

concentration or value or specification

(except for pH)

Limit of detection %

of prescribed

concentration or

value or specification

(except for pH)

(1)

The method of analysis should determine total cyanide in all forms.

(2)

EN ISO 8476.

(3)

The performance characteristics apply to each individual pesticide and will depend on the pesticide concerned. Values for the uncertainty of measurement as low as 30% can be achieved for several pesticides, higher values up to 80% may be allowed for a number of pesticides.

(4)

The performance characteristics apply to the individual substances specified at 25% of the parametric value in Table B of Part 1 of Schedule 1.

(5)

The performance characteristics apply to the individual substances specified at 50% of the parametric value in Table B of Part 1of Schedule 1.

(6)

The performance characteristics apply to the prescribed value of 4 NTU.

(7)

The performance characteristics apply to the specification of 1 NTU for surface waters or ground waters influenced by surface water.

Aluminium | 10 | 10 | 10

Ammonium | 10 | 10 | 10

Antimony | 25 | 25 | 25

Arsenic | 10 | 10 | 10

Benzene | 25 | 25 | 25

Benzo(a)pyrene | 25 | 25 | 25

Boron | 10 | 10 | 10

Bromate | 25 | 25 | 25

Cadmium | 10 | 10 | 10

Chloride | 10 | 10 | 10

Chromium | 10 | 10 | 10

Colour | 10 | 10 | 10

Conductivity | 10 | 10 | 10

Copper | 10 | 10 | 10

Cyanide | 10 | 10 | 10

1.2-dichloroethane | 25 | 25 | 10

Fluoride | 10 | 10 | 10

Hydrogen ion concentration pH (expressed in pH units) | 0.2 | 0.2 |

Iron | 10 | 10 | 10

Lead | 10 | 10 | 10

Manganese | 10 | 10 | 10

Mercury | 20 | 10 | 20

Nickel | 10 | 10 | 10

Nitrate | 10 | 10 | 10

Nitrite | 10 | 10 | 10

Oxidisability | | |

Pesticides and related products | 25 | 25 | 25

Polycyclic aromatic hydrocarbons | 25 | 25 | 25

Selenium | 10 | 10 | 10

Sodium | 10 | 10 | 10

Sulphate | 10 | 10 | 10

Tetrachloroethene | 25 | 25 | 10

Tetrachloromethane | 20 | 20 | 20

Trichloroethene | 25 | 25 | 10

Trihalomethanes:

Total

| | |

25 | 25 | 10

Turbidity | 10 | 10 | 10

Turbidity | 25 | 25 | 25

Table 3

Method of analysis for chemical and indicator parameters: uncertainty of measurement

Parameter |

Uncertainty of measurement

% of parametric value

(except for pH)

(1)

The uncertainty of measurement must not be used as an additional tolerance to the parametric values set out in Schedule 1.

(2)

If the value of uncertainty of measurement cannot be met, the best available technique should be selected (up to 60%).

(3)

The method of analysis should determine total cyanide in all forms.

(4)

EN ISO 8476.

(5)

The performance characteristics apply to each individual pesticide and will depend on the pesticide concerned. Values for the uncertainty of measurement as low as 30% can be achieved for several pesticides, higher values up to 80% may be allowed for a number of pesticides.

(6)

The performance characteristics apply to the individual substances specified at 25% of the parametric value in Table B of Part 1 of Schedule 1.

(7)

The performance characteristics apply to the individual substances specified at 50% of the parametric value in Table B of Part 1 of Schedule 1.

(8)

The uncertainty of measurement must be estimated at the level of 3mg/l of TOC. CEN 1484 Guidelines for the determination of TOC and dissolved organic carbon must be used.

(9)

The uncertainty of measurement must be estimated at the level of 1,0 NTU in accordance with EN ISO 7027.

Aluminium | 25

Ammonium | 40

Antimony | 40

Arsenic | 30

Benzene | 40

Benzo(a)pyrene | 50

Boron | 25

Bromate | 40

Cadmium | 25

Chloride | 15

Chromium | 30

Conductivity | 20

Copper | 25

Cyanide | 30

1,2-dichloroethane | 40

Fluoride | 20

Hydrogen ion concentration pH (expressed in pH units) | 0.2

Iron | 30

Lead | 25

Manganese | 30

Mercury | 30

Nickel | 25

Nitrate | 15

Nitrite | 20

Oxiedisability | 50

Pesticides | 30

Polycyclic aromatic hydrocarbons | 50

Selenium | 40

Sodium | 15

Sulphate | 15

Tetrachloroethene | 30

Trichloroethene | 40

Trihalomethanes: total | 40

Total organic carbon (TOC) | 30

Turbidity | 30