Table C: Indicator Parameters
1 The water must not be aggressive.
2 Necessary only if the water originates from or is influenced by surface water.
3 This parameter need not be measured if the parameter Total Organic Carbon is analysed.
4 This parameter need not be measured for supplies of less than 10,000m3 a day.
Item | Parameter | Units of Measurement | Maximum Concentration or Value
| Aluminium | µg/l | 200
| Ammonium | mg/l | 0.50
| Chloride | mg/l | 250 1
| Clostridium perfringens (including spores) | number/100ml | 0 2
| Colour | Acceptable to consumers and no abnormal change | …
| Conductivity | µS cm-1 at 20°C | 2500 1
| Hydrogen ion concentration | pH units |
4.5 (minimum)
9.5 (maximum) 1
| Iron | µg/l | 200
| Manganese | µg/l | 50
| Odour | Acceptable to consumers and no abnormal change | …
| Oxidisability | mg/l O2 | 5 3
| Sulphate | mg/l | 250 1
| Sodium | mg/l | 200
| Taste | Acceptable to consumers and no abnormal change | …
| Colony Count 22°C | No abnormal change |
| Coliform bacteria | number/250ml | 0
| Total Organic Carbon | No abnormal change | 4
| Turbidity | Acceptable to consumers and no abnormal change |