Parameter | Parametric concentration or value |
Units of
measurement
Further provision | Additional requirements
Aluminium | 200 | µg/l | |
Ammonium | 0.50 | mg/l | |
Chloride | 250 | mg/l | | The water must not be aggressive.
Clostridium perfringens and spores of Clostridium perfringens | 0 | number/100ml | This parameter only needs to be checked if the water originates from, or is influenced by, surface water. |
Colour | Acceptable to consumers and no abnormal change | | |
Conductivity | 2,500 | µS cm-1 at 20°C | | The water must not be aggressive.
Hydrogen ion concentration | 9.5 | pH units | |
The pH of the water must not be lower than 4.5.
The water must not be aggressive.
Iron | 200 | µg/l | |
Manganese | 50 | µg/l | |
Odour | Acceptable to consumers and no abnormal change | | |
Oxidisability | 5.0 | mg/l O2 | This parameter does not need to be checked if total organic carbon is analysed. |
Sulphate | 250 | mg/l | | The water must not be aggressive.
Sodium | 200 | mg/l | |
Taste | Acceptable to consumers and no abnormal change | | |
Colony Count 22° C | No abnormal change | | |
Coliform bacteria | 0 | number/250ml | |
Total organic carbon | No abnormal change | | This parameter does not need not be checked for supplies of less than 10,000m3 a day. |
Turbidity | Acceptable to consumers and no abnormal change | | |