, The Water Intended for Human Consumption (Private Supplies) (Scotland) Regulations 2017

In forcesince 27 Oct 2017

For each parameter in Table 3, the method of analysis used must be capable of measuring activity concentrations with at least the limit of detection specified for that parameter in the second column of that table.

TABLE 3

Minimum performance characteristics: limit of detection

Parameter | Limit of detection (in Bq/l) (Notes 1 and 2) | Notes

Tritium | 10 | Note 3

Radon | 10 | Note 3

gross alpha activity | 0.04 | Note 4

gross beta activity | 0.4 | Note 4

U-238 | 0.02 |

U-234 | 0.02 |

Ra-226 | 0.04 |

Ra-228 | 0.02 | Note 5

Pb-210 | 0.02 |

Po-210 | 0.01 |

C-14 | 20 |

Sr-90 | 0.4 |

Pu-239 / Pu-240 | 0.04 |

Am-241 | 0.06 |

Co-60 | 0.5 |

Cs-134 | 0.5 |

Cs-137 | 0.5 |

I-131 | 0.5 |