Notes:
(i)
The sampling frequency (Y) shall be determined by–
Volume of water supplied each day (m 3 ) | Y
> 1000 – �?� 10,000 | 1 + (1 for each 3,300 m3/d and part thereof of total volume)
> 10,000 – �?� 100,000 | 3 + (1 for each 10,000 m3/d and part thereof of total volume)
> 100,000 | 10 + (1 for each 25,000 m3/d and part thereof of total volume)