Automatic low frequency demand disconnection scheme characteristics:
Parameter | Values SA Continental Europe | Values SA Nordic | Values SA Great Britain | Values SA Ireland | Measuring Unit
Demand disconnection starting mandatory level:
Frequency
49 | 48,7 – 48,8 | 48,8 | 48,85 | Hz
Demand disconnection starting mandatory level:
Demand to be disconnected
5 | 5 | 5 | 6 | % of the Total Load at national level
Demand disconnection final mandatory level:
Frequency
48 | 48 | 48 | 48,5 | Hz
Demand disconnection final mandatory level:
Cumulative Demand to be disconnected
45 | 30 | 50 | 60 | % of the Total Load at national level
Implementation range | ± 7 | ± 10 | ± 10 | ± 7 | % of the Total Load at national level, for a given Frequency
Minimum number of steps to reach the final mandatory level | 6 | 2 | 4 | 6 | Number of steps
Maximum Demand disconnection for each step | 10 | 15 | 10 | 12 | % of the Total Load at national level, for a given step