1 ANNEX, Regulation (EU) 2017/2196

In forcesince 24 Nov 2017

Automatic low frequency demand disconnection scheme characteristics:

Parameter | Values SA Continental Europe | Values SA Nordic | Values SA Great Britain | Values SA Ireland | Measuring Unit

Demand disconnection starting mandatory level:

Frequency

49 | 48,7 – 48,8 | 48,8 | 48,85 | Hz

Demand disconnection starting mandatory level:

Demand to be disconnected

5 | 5 | 5 | 6 | % of the Total Load at national level

Demand disconnection final mandatory level:

Frequency

48 | 48 | 48 | 48,5 | Hz

Demand disconnection final mandatory level:

Cumulative Demand to be disconnected

45 | 30 | 50 | 60 | % of the Total Load at national level

Implementation range | ± 7 | ± 10 | ± 10 | ± 7 | % of the Total Load at national level, for a given Frequency

Minimum number of steps to reach the final mandatory level | 6 | 2 | 4 | 6 | Number of steps

Maximum Demand disconnection for each step | 10 | 15 | 10 | 12 | % of the Total Load at national level, for a given step