1.1. For the purposes of Tables 1 to 4 the following symbols [The characteristics are defined with respect to the appropriate test method.] apply:
(1)‘ΔΤ’temperature rise;
(2)‘Δm’mass loss;
(3)‘tf’duration of flaming;
(4)‘PCS’gross calorific potential;
(5)‘LFS’lateral flame spread;
(6)‘SMOGRA’smoke growth rate.
1.2. For the purposes of Tables 1, 2 and 3 the following symbols [The characteristics are defined with respect to the appropriate test method.] apply:
(1)‘FIGRA’fire growth rate;
(2)‘THR’total heat release;
(3)‘TSP’total smoke production;
(4)‘Fs’flame spread.
1.3. For the purposes of Table 4 the following symbols and test parameters apply:
(1)‘HRRsm30, kW’heat release rate averaged by a 30-s sliding average;
(2)‘SPRsm60, m2/s’smoke production rate averaged by a 60-s sliding average;
(3)‘Peak HRR, kW’maximum of HRRsm30 between test start and end of test, excluded contribution from ignition source;
(4)‘Peak SPR, m2/s’maximum of SPRsm60 between test start and end of test;
(5)‘THR1200, MJ’total heat release (HRRsm30) from test start until end of test, excluded contribution from ignition source;
(6)‘TSP1200, m2’total smoke production (HRRsm60) from test start until end of test;
(7)‘FIGRA, W/s’fire growth rate index defined as the highest value of the quotient between HRRsm30 excluding the contribution of ignition source and time. Threshold values HRRsm30 = 3 kW and THR = 0,4 MJ;
(8)‘FS’flame spread (damaged length);
(9)‘H’flame spread.
For the purposes of Tables 1 to 4 the following definitions apply:
‘material’ means a single basic substance or uniformly dispersed mixture of substances;
‘homogeneous product’ means a product consisting of a single material, having uniform density and composition throughout the product;
‘non-homogeneous product’ means a product that does not satisfy the requirements of a homogeneous product and that is composed of one or more components, substantial and/or non-substantial;
‘substantial component’ means a material that constitutes a significant part of a non-homogeneous product; a layer with a mass per unit area ≥ 1,0 kg/m2 or a thickness ≥ 1,0 mm is considered to be a substantial component;
‘non-substantial component’ means a material that does not constitute a significant part of a non-homogeneous product; a layer with a mass per unit area < 1,0 kg/m2 and a thickness < 1,0 mm is considered to be a non-substantial component;
‘internal non-substantial component’ means a non-substantial component that is covered on both sides by at least one substantial component;
‘external non-substantial component’ means a non-substantial component that is not covered on one side by a substantial component.
Two or more non-substantial layers that are adjacent to each other, where there are no substantial components in between the layers, shall be considered as one non-substantial component and shall, therefore, be classified in accordance with the criteria for a layer that is a non-substantial component.
[For homogeneous products and substantial components of non-homogeneous products.] [For any external non-substantial component of non-homogeneous products.] [(2a) Alternatively, any external non-substantial component having a PCS ≤ 2,0 MJm– 2, provided that the product satisfies the following criteria of EN 13823(SBI): FIGRA ≤ 20 Ws– 1; and LFS < edge of specimen; and THR600s ≤ 4,0 MJ; and s1; and d0.] [For any internal non-substantial component of non-homogeneous products.] [For the product as a whole.] [s1 = SMOGRA ≤ 30m2s– 2 and TSP600s ≤ 50m2; s2 = SMOGRA ≤ 180m2s– 2 and TSP600s ≤ 200m2; s3 = not s1 or s2.] [d0 = No flaming droplets/particles in EN 13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN 13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.] [No ignition of the paper = no additional classification; Ignition of the paper = d2 classification.] [Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.]
Class | Test method(s) | Classification criteria | Additional classification
A1 |
EN ISO 1182;
and
ΔΤ ≤ 30 °C; and
Δm ≤ 50 %; and
tf = 0 (i.e. no sustained flaming)
EN ISO 1716 |
PCS ≤ 2,0 MJkg– 1; and
PCS ≤ 2,0 MJkg– 1; and
PCS ≤ 1,4 MJm– 2; and
PCS ≤ 2,0 MJkg– 1
A2 |
EN ISO 1182;
or
ΔΤ ≤ 50 °C; and
Δm ≤ 50 %; and
tf ≤ 20 s
EN ISO 1716;
and
PCS ≤ 3,0 MJkg– 1; and
PCS ≤ 4,0 MJm– 2; and
PCS ≤ 4,0 MJm– 2; and
PCS ≤ 3,0 MJkg– 1
EN 13823 (SBI) |
FIGRA ≤ 120 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
B |
EN 13823 (SBI);
and
FIGRA ≤ 120 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
C |
EN 13823 (SBI);
and
FIGRA ≤ 250 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 15 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
D |
EN 13823 (SBI);
and
FIGRA ≤ 750 Ws– 1 |
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
E |
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s | Flaming droplets/particles
F |
EN ISO 11925-2:
Exposure = 15 s
Fs > 150 mm within 20 s |
[For homogeneous products and substantial components of non-homogeneous products.] [For any external non-substantial component of non-homogeneous products.] [For any internal non-substantial component of non-homogeneous products.] [For the product as a whole.] [Test duration = 30 minutes.] [Critical flux is defined as the radiant flux at which the flame extinguishes or the radiant flux after a test period of 30 minutes, whichever is the lower (i.e. the flux corresponding with the furthest extent of spread of flame).] [s1 = Smoke ≤ 750 %.min; s2 = not s1.] [Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.]
Class | Test method(s) | Classification criteria | Additional classification
A1FL |
EN ISO 1182;
and
ΔΤ ≤ 30 °C; and
Δm ≤ 50 %; and
tf = 0 (i.e. no sustained flaming)
EN ISO 1716 |
PCS ≤ 2,0 MJkg– 1; and
PCS ≤ 2,0 MJkg– 1; and
PCS ≤ 1,4 MJm– 2; and
PCS ≤ 2,0 MJkg– 1
A2FL |
EN ISO 1182;
or
ΔΤ ≤ 50 °C; and
Δm ≤ 50 %; and
tf ≤ 20 s
EN ISO 1716;
and
PCS ≤ 3,0 MJkg– 1; and
PCS ≤ 4,0 MJm– 2; and
PCS ≤ 4,0 MJm– 2; and
PCS ≤ 3,0 MJkg– 1
EN ISO 9239-1 | Critical flux ≥ 8,0 kWm– 2 | Smoke production
BFL |
EN ISO 9239-1
and
Critical flux ≥ 8,0 kWm– 2 | Smoke production
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
CFL |
EN ISO 9239-1
and
Critical flux ≥ 4,5 kWm– 2 | Smoke production
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
DFL |
EN ISO 9239-1
and
Critical flux ≥ 3,0 kWm– 2 | Smoke production
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s
EFL |
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s |
FFL |
EN ISO 11925-2:
Exposure = 15 s
Fs > 150 mm within 20 s |
[For homogeneous products and substantial components of non-homogeneous products.] [For any external non-substantial component of non-homogeneous products.] [For any internal non-substantial component of non-homogeneous products.] [For the product as a whole.] [s1 = SMOGRA ≤ 105 m2s– 2 and TSP600s ≤ 250 m2; s2 = SMOGRA ≤ 580 m2s– 2 and TSP600s ≤ 1600 m2; s3 = not s1 or s2.] [d0 = No flaming droplets/particles in EN13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification.] [No ignition of the paper = no additional classification; Ignition of the paper = d2 classification.] [Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack.]
Class | Test method(s) | Classification criteria | Additional classification
A1L |
EN ISO 1182;
and
ΔT ≤ 30 °C; and
Δm ≤ 50 %; and
tf = 0 (i.e. no sustained flaming)
EN ISO 1716 |
PCS ≤ 2,0 MJkg– 1; and
PCS ≤ 2,0 MJkg– 1; and
PCS ≤ 1,4 MJm– 2; and
PCS ≤ 2,0 MJkg– 1
A2L |
EN ISO 1182;
or
ΔT ≤ 50 °C; and
Δm ≤ 50 %; and tf ≤ 20 s
EN ISO 1716;
and
PCS ≤ 3,0 MJkg– 1; and
PCS ≤ 4,0 MJm– 2; and
PCS ≤ 4,0 MJm– 2; and
PCS ≤ 3,0 MJkg– 1
EN 13823 (SBI) |
FIGRA ≤ 270 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
BL |
EN 13823 (SBI);
and
FIGRA ≤ 270 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 7,5 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
CL |
EN 13823 (SBI);
and
FIGRA ≤ 460 Ws– 1; and
LFS < edge of specimen; and
THR600s ≤ 15 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
DL |
EN 13823 (SBI);
and
FIGRA ≤ 2100 Ws– 1
THR600s ≤ 100 MJ
Smoke production; and
Flaming droplets/particles
EN ISO 11925-2:
Exposure = 30 s
Fs ≤ 150 mm within 60 s
EL |
EN ISO 11925-2:
Exposure = 15 s
Fs ≤ 150 mm within 20 s | Flaming droplets/particles
FL |
EN ISO 11925-2:
Exposure = 15 s
Fs > 150mm within 20 s |
[For the product as a whole, excluding metallic materials, and for any external component (i.e. sheath) of the product.] [s1 = TSP1200 ≤ 50 m2 and Peak SPR ≤ 0,25 m2/s s1a = s1 and transmittance in accordance with EN 61034-2 ≥ 80 % s1b = s1 and transmittance in accordance with EN 61034-2 ≥ 60 % < 80 % s2 = TSP1200 ≤ 400 m2 and Peak SPR ≤ 1,5 m2/s s3 = not s1 or s2] [d0 = No flaming droplets/particles within 1200 s; d1 = No flaming droplets/particles persisting longer than 10 s within 1200 s; d2 = not d0 or d1.] [EN 60754-2: a1 = conductivity < 2,5 μS/mm and pH > 4,3; a2 = conductivity < 10 μS/mm and pH > 4,3; a3 = not a1 or a2.] [The smoke class declared for class B1ca cables must originate from the EN 50399 test (30 kW flame source).] [The smoke class declared for class B2ca, Cca, Dca cables must originate from the EN 50399 test (20,5 kW flame source).]
Class | Test method(s) | Classification criteria | Additional classification
Aca | EN ISO 1716 | PCS ≤ 2,0 MJ/kg |
B1ca |
EN 50399 (30 kW flame source)
and
FS ≤ 1,75 m and
THR1200s ≤ 10 MJ and
Peak HRR ≤ 20 kW and
FIGRA ≤ 120 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2 | H ≤ 425 mm
B2ca |
EN 50399 (20,5 kW flame source)
and
FS ≤ 1,5 m; and
THR1200s ≤ 15 MJ; and
Peak HRR ≤ 30 kW; and
FIGRA ≤ 150 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2 | H ≤ 425 mm
Cca |
EN 50399 (20,5 kW flame source)
and
FS ≤ 2,0 m; and
THR1200s ≤ 30 MJ; and
Peak HRR ≤ 60 kW; and
FIGRA ≤ 300 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2 | H ≤ 425 mm
Dca |
EN 50399 (20,5 kW flame source)
and
THR1200s ≤ 70 MJ; and
Peak HRR ≤ 400 kW; and
FIGRA ≤ 1300 Ws– 1
Smoke production and Flaming droplets/particles and Acidity (pH and conductivity)
EN 60332-1-2 | H ≤ 425 mm
Eca | EN 60332-1-2 | H ≤ 425 mm |
Fca | EN 60332-1-2 | H > 425 mm |