1 ANNEX In the Annex to Decision 2003/43/EC, the following Tables and note shall be added:, Decision_act (EU) 2003/593

In force

"

TABLE 2

Classes of reaction-to-fire performance of gypsum plasterboard products

>TABLE>

Note: End Use Application

The gypsum plasterboards shall be mounted and fixed using one of the two following methods:

(a)

Mechanically fixed to a supporting substructure

The boards, or (in the case of multi-layer systems) at least the outermost layer of boards, shall be mechanically fixed to a metal substructure (made from components detailed in EN 14195) or a timber substructure (in accordance with EN 336 and ENV 1995-5).

When the substructure provides supporting members in one direction only, the maximum span between the supporting members shall not exceed a dimension equal to 50 times the thickness of the boards. When the substructure includes supporting members in two directions the maximum span in either direction shall not exceed a dimension equal to 100 times the thickness of the boards.

The mechanical fixings shall be screws or nails, which shall be fixed through the thickness of the boards into the substructure at centres not exceeding 300 mm measured along the length of each supporting member.

All joints between adjoining boards shall be fully filled with jointing compound as specified in EN 13963.

The cavity formed behind the boards by the substructure may provide an air space, or may be filled with an insulating material with a reaction to fire classification of at least class A2-s1, d0.

(b)

Directly fixed or bonded to a solid substrate (dry lining system)

The boards shall be fixed directly to a solid substrate with a reaction to fire classification of at least class A2-s1, d0.

The boards may be fixed using screws or nails fixed through the thickness of the boards into the solid substrate or may be bonded to the substrate using 'dabs' of gypsum based adhesive compound. In either case the screw or nail fixings or the adhesive 'dabs' shall be positioned at maximum 600 mm vertical and horizontal centres.

All joints between adjoining boards shall be fully filled with jointing compound as specified in EN 13963.

TABLE 3

Classes of reaction-to-fire performance of high-pressure decorative laminate panels

>TABLE>

TABLE 4

Classes of reaction-to-fire performance of structural timber products((Applies to all species covered by the product standards.))

>TABLE>"