1 ANNEX, Decision_act (EU) 2003/43

In forcesince 23 May 2007

The tables set out in this annex list construction products and/or materials which satisfy all the requirements for the performance characteristic reaction to fire without need for testing.

[Mounted without an air gap directly against class A1 or A2-s1, d0 products with minimum density 10 kg/m3 or at least class D-s2, d2 products with minimum density 400 kg/m3.] [A substrate of cellulose insulation material of at least class E may be included if mounted directly against the wood-based panel, but not for floorings.] [Mounted with an air gap behind. The reverse face of the cavity shall be at least class A2-s1, d0 products with minimum density 10 kg/m3.] [Mounted with an air gap behind. The reverse face of the cavity shall be at least class D-s2, d2 products with minimum density 400 kg/m3.] [Veneered, phenol- and melamine-faced panels are included for class excl. floorings.] [A vapour barrier with a thickness up to 0,4 mm and a mass up to 200 g/m2 can be mounted in between the wood-based panel and a substrate if there are no air gaps in between.] [Class as provided for in Table 1 of the Annex to Decision 2000/147/EC.] [Class as provided for in Table 2 of the Annex to Decision 2000/147/EC.]

Product | EN product standard | End use condition |

Minimum density

(kg/m3)

Minimum thickness

(mm)

Class

(excluding floorings)

Class

(floorings)

Cement-bonded particleboard | EN 634-2 | without an air gap behind the panel | 1000 | 10 | B-s1, d0 | Bfl-s1

Fibreboard, hard | EN 622-2 | without an air gap behind the wood-based panel | 900 | 6 | D-s2, d0 | Dfl-s1

Fibreboard, hard | EN 622-2 | with a closed air gap not more than 22 mm behind the wood-based panel | 900 | 6 | D-s2, d2 | —

Particleboard,, | EN 312 | without an air gap behind the wood-based panel | 600 | 9 | D-s2, d0 | Dfl-s1

Fibreboard, hard and medium,, |

EN 622-2

EN 622-3

MDF,, | EN 622-5

MDF,, | EN 300

Plywood,, | EN 636 | -“- | 400 | 9 | D-s2, d0 | Dfl-s1

Solid wood panel,, | EN 13353 | 12

Flaxboard,, | EN 15197 | -“- | 450 | 15 | D-s2, d0 | Dfl-s1

Particleboard, | EN 312 | with a closed or an open air gap not more than 22 mm behind the wood-based panel | 600 | 9 | D-s2, d2 | —

Fibreboard, hard and medium, |

EN 622-2

EN 622-3

MDF, | EN 622-5

OSB, | EN 300

Plywood, | EN 636 | -“- | 400 | 9 | D-s2, d2 | —

Solid wood panel, | EN 13353 | 12

Particleboard, | EN 312 | with a closed air gap behind the wood-based panel | 600 | 15 | D-s2, d0 | Dfl-s1

Fibreboard, medium, | EN 622-3

MDF, | EN 622-5

OSB, | EN 300

Plywood, | EN 636 | -“- | 400 | 15 | D-s2, d1 | Dfl-s1

Solid wood panel, | EN 13353 | D-s2, d0

Flaxboard, | EN 15197 | -“- | 450 | 15 | D-s2, d0 | Dfl-s1

Particleboard, | EN 312 | with an open air gap behind the wood-based panel | 600 | 18 | D-s2, d0 | Dfl-s1

Fibreboard, medium, | EN 622-3

MDF, | EN 622-5

OSB, | EN 300

Plywood, | EN 636 | -“- | 400 | 18 | D-s2, d0 | Dfl-s1

Solid wood panel, | EN 13353

Flaxboard, | EN 15197 | -“- | 450 | 18 | D-s2, d0 | Dfl-s1

Particleboard | EN 312 | any | 600 | 3 | E | Efl

OSB | EN 300

MDF | EN 622-5 | -“- | 400 | 3 | E | Efl

250 | 9 | E | Efl

Plywood | EN 636 | -“- | 400 | 3 | E | Efl

Fibreboard, hard | EN 622-2 | -“- | 900 | 3 | E | Efl

Fibreboard, medium | EN 622-3 | -“- | 400 | 9 | E | Efl

Fibreboard, soft | EN 622-4 | -“- | 250 | 9 | E | Efl

[Determined according to EN ISO 536 and with no more than 5 % organic additive content.] [Classes as provided for in Table 1 of the Annex to Commission Decision 2000/147/EC.]

Gypsum plasterboard | Nominal board thickness (mm) | Gypsum core |

Paper grammage

(g/m2)

Substrate | Class (excluding floorings)

Density (kg/m3) | Reaction to fire class

Conforming to EN 520 (except perforated boards) | ≥ 6,5 < 9,5 | ≥ 800 | A1 | ≤ 220 | Any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 | A2-s1, d0

> 220 ≤ 320 | B-s1, d0

≥ 9,5 | ≥ 600 | ≤ 220 | Any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 or any insulating product of at least class E-d2 mounted according to method 1 | A2-s1, d0

> 220 ≤ 320 | B-s1, d0

The gypsum plasterboards (hereinafter — ‘gypsum boards’) shall be mounted and fixed using one of the three following methods:

Method 1 — Mechanically fixed to a supporting substructure

The gypsum boards, or (in the case of multi-layer systems) at least the outermost layer of boards, shall be mechanically fixed to a metal substructure (made from components detailed in EN 14195) or to a timber substructure (in accordance with EN 336 and EN 1995-1-1).

When the substructure provides supporting members in one direction only, the maximum span between the supporting members shall not exceed a dimension equal to 50 times the thickness of the gypsum boards.

When the substructure includes supporting members in two directions the maximum span in either direction shall not exceed a dimension equal to 100 times the thickness of the gypsum boards.

The mechanical fixings shall be screws, staples or nails, which shall be fixed through the thickness of the gypsum boards into the substructure at centres not exceeding 300 mm measured along the length of each supporting member.

Behind the gypsum boards may be an air space, or an insulating product. The substrate may be:

(a)

any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 in case of gypsum boards of ≥ 6,5 mm and < 9,5 mm nominal thickness and ≥ 800 kg/m3 core density, or

(b)

any wood-based product with density ≥ 400 kg/m3 or any product of at least class A2-s1, d0 in case of gypsum boards of ≥ 9,5 mm nominal thickness and ≥ 600 kg/m3 core density, or

(c)

any insulating material of at least class E-d2 in case of gypsum boards of ≥ 9,5 mm nominal thickness and ≥ 600 kg/m3 core density.

Each joint between adjoining gypsum boards shall have a gap width ≤ 4 mm. This provision applies for any joint regardless of that the joint is or is not supported directly by a substructure supporting member and regardless of that the joint is or is not filled with a jointing material.

In cases (a) and (b) each joint between adjoining gypsum boards, which is not supported directly by a substructure supporting member and which has a gap width > 1 mm, shall be fully filled with a jointing material as specified in EN 13963 (the other joints may remain unfilled).

In case (c) all joints between adjoining gypsum boards shall be fully filled with a jointing material as specified in EN 13963.

Method 2 — Mechanically fixed to a solid wood-based substrate

The gypsum boards shall be mechanically fixed to a solid wood-based substrate with density ≥ 400 kg/m3.

There shall be no cavity between the gypsum boards and the substrate.

The mechanical fixings shall be screws, staples or nails. The distance between the mechanical fixings shall correspond to the rules given above for method 1.

Each joint between adjoining gypsum boards shall have a gap width ≤ 4 mm and may remain unfilled.

Method 3 — Mechanically fixed or bonded to a solid substrate (dry lining system)

The gypsum boards shall be fixed directly to a solid substrate with a reaction to fire classification of at least class A2-s1, d0.

The gypsum boards may be fixed using screws or nails fixed through the thickness of the gypsum boards into the solid substrate or may be bonded to the substrate using ‘dabs’ of a gypsum based adhesive as specified in EN 14496.

In either case the screw or nail fixings or the adhesive ‘dabs’ shall be positioned at maximum 600 mm vertical and horizontal centres.

All joints between adjoining gypsum boards may remain unfilled.

[Either directly fixed (i.e. with no air gap) to a material having a reaction to fire of A2-s1, d0 or better and a density of at least 600 kg/m3, or mounted on a timber or metal batten support frame, with a non-ventilated (i.e. void open only at the top) air gap of at least 30 mm, the reverse face of the cavity so formed having a reaction to fire classification of A2-s1, d0 or better.] [Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.] [Complying with European Standard EN 438-7.]

High pressure decorative laminate panels | Product detail |

Minimum density

(kg/m3)

Minimum overall thickness

(mm)

Class

(excluding floorings)

Interior grade non-FR Compact HPL panels | Compact HPL meeting EN 438-4 type CGS | 1350 | 6 | D-s2, d0

Interior grade non-FR HPL composite panels with wood-based substrates | Composite panels comprising non-FR grade HPL meeting the requirements of EN 438-3, adhesively bonded to both sides of non-FR grade wood-based core of minimum thickness 12 mm complying with EN 13986, using PVAc or thermosetting adhesive at an application rate of 60 to 120 g/m2 |

Wood-based core minimum density 600

HPL minimum density 1350

12 mm wood-based core with HPL ≥ 0,5 mm bonded to both sides | D-s2, d0

[Applies to all species covered by the product standards.] [Classes as provided for in Table 1 of the Annex to Decision 2000/147/EC.] [Conditioned according to EN 13238.]

Product detail |

Minimum mean density

(kg/m3)

Minimum overall thickness

(mm)

Class

(excluding floorings)

Structural timber | Visual and machine graded structural timber with rectangular cross-sections shaped by sawing, planing or other methods or with round cross-sections | 350 | 22 | D-s2, d0

  • celex=32000D0147
  • num:eu=2000/147